EasyManua.ls Logo

Bryant 650A - Electrical; Compressor & Refrigerant; Outdoor Coil & Fan; Optional Equipment

Bryant 650A
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
—5—
SPECIFICATIONS Continued
*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable
(NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
Length shown is as measured 1 way along the wire path between the unit and the service panel for a voltage drop not to exceed 2 percent.
** Time-delay fuse or circuit breaker.
†† The factory refrigerant charge is for 15 ft of interconnecting tubing. For tubing lengths other than 15 ft, refer to the Residential Split-Systems Long-Line
Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron (R-410A).
‡‡ Install with Ball-Bearing Fan Motor.
*** Use with low-ambient pressure switch.
NOTE:
Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
UNIT SIZE-SERIES 042-D, E 048-D, E, F 060-D, E
Operating Weight (Lb) 218 266 295
ELECTRICAL
Unit Volts—Hertz—Phase 208/230—60—1
Operating Voltage Range* 187—253
Compressor Rated Load Amps 21.1 20.5/21.8 27.6
Compressor Locked Rotor Amps 104.0 109.0/117.0 158.0
Condenser Fan Motor—Full Load Amps 1.1 1.4 1.4
Minimum Unit Ampacity for Wire Sizing 27.5 27.0/28.6 35.9
Minimum Wire Size (60°C Copper) (AWG)† 10 10 8
Minimum Wire Size (75°C Copper) (AWG)† 10 10 8
Maximum Wire Length (60°C) (Ft)‡ 71 74/69 86
Maximum Wire Length (75°C) (Ft)‡ 68 70/66 82
Maximum Branch Circuit Fuse Size** 40 40 60
COMPRESSOR & REFRIGERANT
Compressor Type Scroll
Refrigerant Type Puron
Refrigerant Amount (Lb)†† 8.63 13.25 13.25
OUTDOOR COIL & FAN
Coil Face Area (Sq Ft) 12.12 18.18 18.18
Fins per In.—Rows—Circuits 20—2—3 20—2—4 20—2—5
Fan Motor—HP & RPM 1/5 and 825 1/4 and 1100 1/4 and 1100
Rated Airflow (CFM) 2800 3300 3300
OPTIONAL EQUIPMENT
Support Feet—4 In. (4) KSASF0101AAA
Snow Stand—18 In. KHASS0206MPK
Time Delay Relay KAATD0101TDR
Ball-Bearing Fan Motor HC38GE231 HC40GE232
MotorMaster®—Low-Ambient Controller‡‡ KSALA0401AAA
Outdoor Thermostat KHAOT0301FST
Secondary Outdoor Thermostat KHAOT0201SEC
Crankcase Heater KAACH1201AAA Standard
Start Assist—Capacitor/Relay Type KSAHS1501AAA KSAHS1601AAA
Start Assist—PTC Type KAACS0201PTC
Bi-Flow TXV (Hard Shutoff) KSATX0301PUR KSATX0401PUR KSATX0501PUR
Evaporator Freeze Thermostatz*** KAAFT0101AAA
Isolation Relay*** KHAIR0101AAA
Liquid-Line Solenoid Valve (LSV) KHALS0401LLS
Low-Ambient Pressure Switch KSALA0301410
Coastal Filter KAACF0801MED
Pressure Guard™ Kit KHAPG0101PGS KHAPG0201PGS
Evolution Controls See chart.

Other manuals for Bryant 650A

Related product manuals