47
ELECTRICAL DATA (cont.)
569J*25A COOLING WITHOUT POWERED CONVENIENCE OUTLET
V --- P h --- H z
VOLTAGE RANGE COMP 1 COMP 2 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MC A Fuse
208/230--- 3---60 187 253 30.1 225 30.1 225 325 1.5 73.7 100
4 6 0 --- 3 --- 6 0 414 506 16.7 114 16.7 114 325 0.8 40.8 50
5 7 5 --- 3 --- 6 0 518 633 12.2 80 12.2 80 325 0.7 30.3 40
569J*25A COOLING WITH POWERED CONVENIENCE OUTLET
V --- P h --- H z
VOLTAGE RANGE COMP 1 COMP 2 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MC A Fuse
208/230--- 3---60 187 253 30.1 225 30.1 225 325 1.5 78.5 100
4 6 0 --- 3 --- 6 0 414 506 16.7 114 16.7 114 325 0.8 43.0 50
5 7 5 --- 3 --- 6 0 518 633 12.2 80 12.2 80 325 0.7 32.0 40
569J*25D COOLING WITHOUT POWERED CONVENIENCE OUTLET
V --- P h --- H z
VOLTAGE RANGE COMP 1 COMP 2 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MC A Fuse
208/230--- 3---60 187 253 30.1 225 30.1 225 325 1.5 73.7 100
4 6 0 --- 3 --- 6 0 414 506 16.7 114 16.7 114 325 0.8 40.8 50
5 7 5 --- 3 --- 6 0 518 633 12.2 80 12.2 80 325 0.7 30.3 40
569J*25D COOLING WITH POWERED CONVENIENCE OUTLET
V --- P h --- H z
VOLTAGE RANGE COMP 1 COMP 2 OFM (ea) POWER SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MC A Fuse
208/230--- 3---60 187 253 30.1 225 30.1 225 325 1.5 78.5 100
4 6 0 --- 3 --- 6 0 414 506 16.7 114 16.7 114 325 0.8 43.0 50
5 7 5 --- 3 --- 6 0 518 633 12.2 80 12.2 80 325 0.7 32.0 40