40
NOTE: For more information, see General Fan Performance Notes.
PULLEY ADJUSTMENT - BELT DRIVE
582J UNIT
MOTOR/
DRIVE
COMBO
MOTOR PULLEY TURNS OPEN
00.511.522.533.544.55
04
1 phase
Medium
Static
1175 1135 1094 1054 1013 973 932 892 851 811 770
High
Static
1466 1423 1380 1337 1294 1251 1207 1164 1121 1078
1035
05
Medium
Static
1175 1135 1094 1054 1013 973 932 892 851 811
770
High
Static
1466 1423 1380 1337 1294 1251 1207 1164 1121 1078
1035
06
Medium
Static
1466 1423 1380 1337 1294 1251 1207 1164 1121 1078
1035
High
Static
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A
04
3 phase
Medium
Static
1175 1135 1094 1054 1013 973 932 892 851 811
770
High
Static
1466 1423 1380 1337 1294 1251 1207 1164 1121 1078
1035
05
Medium
Static
1303 1265 1226 1188 1150 1112 1073 1035 997 958
920
High
Static
1550 1516 1482 1447 1413 1379 1345 1311 1276 1242
1208
06
Medium
Static
1466 1423 1380 1337 1294 1251 1207 1164 1121 1078
1035
High
Static
1550 1525 1501 1476 1451 1427 1402 1377 1352 1328
1303
– Factory setting
N/A – Not Available
PERFORMANCE DATA (cont)