EasyManuals Logo

Bticino Legrand MyHome User Manual

Bticino Legrand MyHome
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
1312
Thermostat with display
Installer manual
5.2 Automatic changeover function
(available starting from version 1.3 of MyHOME_Suite)
(Not available in MyHOME systems).
The thermostat can be programmed for automatic changeover between the heating and the cooling
functions. When programmed in this way, the (
/ ) icons are not displayed.
Depending on the temperature measured, the heating or cooling system in operation symbols
(
/ ) will appear, to indicate that the corresponding function is active.
Note: Automatic changeover mode cannot be configured physically, but must be enabled during
the advanced configuration (using the MyHOME_Suite software).
This function can be used when it is necessary for the thermostat to automatically manage the
changeover between heating and cooling, and is for example useful in case of 4 tube fan-coils.
Using the MyHOME_Suite software, it is possible to set the range of temperature at different levels,
for the activation of the heating and the cooling systems, depending of the thermal inertia of one’s
own system, and specific requirements.
COOLING
HEATING
CHANGEOVER POINT
CHANGEOVER
POINT
COOLING
HEATING
HEATING
& COOLING
CHANGEOVER
BAND
COMPLETE
CHANGEOVER
DEADBAND
COOLING
HEATING
DEADBAND

Questions and Answers: