Troubleshooting | 12
Instruction Manual TYR WT 0100-0730 CP CV_EN_en 35 | 44
Problem Possible Cause Remedy
Loss of capacity. Leak in the system. ● Find the leaks and stop
them.
Activated safety valve. ● Check differential pressure
and see causes marked with
*.
Possibly set the safety
valve’s opening pressure.
Dirty inlet filter or blocked
pipes.
● Clean and possibly replace
filters and pipes.
Loose belts. ● Replace belts.
Too high differential pres-
sure*.
● See symptoms and causes
marked with *.
Continuously activated safety
valve.
Too high rpm and thereby too
high amount of air (concerns
frequency-controlled blowers).
● Lower the rpm.
Too high differential pressure* ● Find the cause of the in-
creased differential pressure
and repair it.
The valve setting is below the
actual operating point.
● Adjust the max limits of fthe
valve within the blower.
Monitor the absorbed pow-
er and ensure that the set-
ting does not allow over-
loading of the pump.
Abnormally high differential
pressure*
STOP THE MACHINE IMMEDI-
ATELY !
Safety valves do not open de-
spite too high differential pres-
sure.
● Dismantle and clean valve
and possibly readjust.
Blockages on inlet side or out-
let side of the blower.
● Clean the pipe system and
look for mechanical or con-
trol system related blockag-
es or obstructions that can
lead to increased loss of
pressure.
Fault on check valve. ● Replace check valve.
The motor is running the
wrong way.
Wrong power supply. Switch two phases to reverses
the direction of revolutions.
Abnormal motor temperature. Motor fault or fault in motor
bearings.
● Repair and replace the mo-
tor.
The motor is incorrectly electri-
cally wired.
● Check and reconnect.
Overloading. ● Look for causes of increased
differential pressure in the
system and repair.
Wrong power supply. ● The power supply must be
consistent with data on mo-
tor’s type sign.
Too high ambient temperature
(+40°C).
● Improve ventilation in the
machine room.
Fault on motor fan. ● Repair and replace the mo-
tor fan.