CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 47 of 48
TURN LEDS ON/OFF
This function assists with fault-finding and wiring faults.
Enter AL3 (4444) > Engineer Functions > Turn LEDS ON/OFF.
When accepted, select the loop (1 or 2 or ALL) and panel displays (similar to the following) will appear.
At each display, press the 5and6 scroll buttons to toggle, then press the Accept4button to proceed.
Options are available to turn the device (polling) LEDS either ON or OFF, at Both Ends/End A Only/End B
Only and the Poll Group (see tables below for device numbers).
Press the Escape 3button to exit the function.
Turn LEDs : Both Ends
Poll Group : 0
Turn LEDs : OFF
Turn LEDs : ON
Poll Group Device No.
0 1 to 15
1 16 to 31
2 32 to 47
3 48 to 63
4 64 to 79
5 80 to 95
6 96 to 111
7 112 to 127
Poll Group Device No.
8 128 to 143
9 144 to 159
10 160 to 175
11 176 to 191
12 192 to 207
13 208 to 223
14 224 to 239
15 240 to 255
CAUTION: ENSURE YOU DO
NOT TURN ON MORE THAN
THREE (3) POLL GROUPS AT
THE SAME TIME, OTHERWISE
TOO MUCH CURRENT WILL
PASS THROUGH THE LOOP.
STANDBY BATTERY CALCULATION GUIDE
Hint! Hint! An XFP Loop & Battery Calculator Tool is available for download on C-TEC’s website
to assist with battery calculations (available @ www.c-tec.com).
MAINTENANCE
Periodic system maintenance should be carried out on the system as prescribed in the local design,
maintenance and installation regulations.
The Fire Alarm panel’s standby batteries should be checked for integrity of the connections and deposits
indicating venting. A periodic load test with the mains supply disconnected should also be performed
to ensure adequate battery capacity. Both batteries should be renewed if there is any doubt about
their integrity.
The panel’s event log should be checked for any faults that have automatically cleared, and these dealt
with accordingly.
DIAGNOSTICS FUNCTIONS
These functions are for trained engineers only and are not detailed in this manual. Contact C-TEC
Technical for further assistance.

Other manuals for C-TEC XFP501E/CA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the C-TEC XFP501E/CA and is the answer not in the manual?

C-TEC XFP501E/CA Specifications

General IconGeneral
BrandC-TEC
ModelXFP501E/CA
CategoryControl Panel
LanguageEnglish

Related product manuals