5!
COMMISSIONING!
When!the!installation!procedure!is!com ple ted ,!after!ha ving !che cke d!th at!all!con ne ctio ns!h ave !be en !m ad e!co rrec tly,!to!
make!DATA!EASY!operational!commission!the!plant!by!performing!the!steps!described!below:!
Ø Fill!in!the!building!details!form!(see!page!11).
If!meters!are!found!with!the!same!primary!address!(IDB),!proceed!with!the!primary!address!setup!operations
(see!page!10)
The!presence!in!the!system!of!even!one!incorrectly!connected!module!or!of!modules!with!duplicated!primary
address,!will!make!it!impossible!to!transfer!data.
Ø Check!the!correct!connection!of!Conteca!heat!meters!and!additional!services!by!referring!to!the!technical
datasheets!attached!to!the!meter.
Ø Check!that!the!voltage!on!terminals!(15)!and!(16)!complies!with!the!electrical!specifications!(24Vdc!+/-!10%,
24Vac!(min!20Vac,!max!40Vac)!or,!alternatively,!PoE!(IEEE!802.3)
Ø Power!on!DATA!EASY
Ø Set!the!system!Date!by!selecting!the!SETTINGS!>!General!>!System !date!page!in!the!main!menu!or!by!accessing
the!web!server!(se e!D A TA !E AS Y!WEB!SERVER!manu al)
Ø Start!the!meters!search!by!clicking!OK!in!c orresponden c e !with!the!SEARCH!icon!or!by!accessing!the!web!server.
(see!DATA!E A SY !W E B!S ER VE R !m an ua l)
Ø When!the!search!is!comp leted !a!list!of!recog nise d!m ete rs!w ill!be!displaye d!w ith!an!ind ication !of!the
communication!status!(OK!or!ERROR)
If!some!o r!all!o f!th e !d e vice s !are !n o t!d e te ct ed
-
Re-check! correct! connection! of! the! bus! between! DATA! EASY! and! meters! and! the! com m unication
settings!(BAUD!RATE!and!add ress).
Click!OK!to!save!the!recognised!me ters!to !the !dev ice !
On! completion! of! the! phases! described! above! we! recommend! accessing! the! DATA! EASY! web! server! to!
complete! the! configuration! and! set! up! the! necessary! parameters! for! correct! o peration! of! the! system! (see!
DATA!EASY!WEB!SERVER!manual)!
LANGUAGE!SELECTION!
The!language!choice!can!be!made!both!via!the!keypad!provided!and!via!the!WEB!interface.!
In!the!first!case ,!o n c e!t he !se c u rity!p a ss w o rd !h as !be e n !e nt er ed ,!to !c h an g e!t he !language!simply!press! !or! !in!the!
main!menus:!INFO,!METERS!LIST,!SEARCH!and!SETTINGS.!The!available!la n g u a g e s!a re!English!and!Italian .!