Page 15 - Manual FB00801-EN - ver. 1 - 07/2017 - © CAME S.p.A. - The contents of this manual are subject to change at any time without prior notice.
The graph and table K can help you decide on the type of program or value of the
parameter to be added.
Press P to exit programming.
N.B. All parameters related to the configuration of the type of temperature management
algorithm are saved in the permanent memory of the device.
Press P J to confirm the mini-
mum ON time and switch to
adjusting the proportional band.
Use the
buttons to adjust
the value of the proportional band
to between 1 and 3 °C.
Press P I to confirm the set
cycle time and switch to adjusting
the minimum ON time.
Use the
buttons to choose
the minimum ON time between 1
and 5 minutes.
Use the
buttons to choose
the duration of the cycle - 5,
10, 15, 20, 25, 30, 35 or 40
minutes H.