23
Figure 22: Lockout Condition
To eliminate the lockout error,
1) Press the red bar, indicating a Lockout condition
2) Press the [Lockouts] button
Figure 23: Lockout History
3) Press [Clear Lockout]
Table 13: Alert/Hold Codes
30 Burner switch turned ON
Invalid subsystem reset request occurred
50 Modulation Fault (DR300 – 1000 ONLY)
68 Setpoint was overridden due to sensor fault
69 Modulation was overridden due to sensor fault
123 Modulation rate was limited due to outlet limit
124 Modulation rate was limited due to Delta-T limit
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to
sensor failure
229 Lead lag slave communication timeout.
275-
LCI off, safety circuit is open
283 Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of
Ignition period
292
Abnormal Recycle: Flame was lost during Main
293 Abnormal Recycle: Flame was lost early in Run
Abnormal Recycle: Flame was lost during Run
303-
310
+
Interlock Off, safety circuit is open
324,
374-
379
Hardware flame bias. Flame sensor wire needs to
be re-routed.
352
460 LCI lost in run
550 Delta T inlet/outlet limit was exceeded
* If an internal hardware fault is detected contact Camus®
technical support for troubleshooting procedure.
+
The alarm LED and alarm contacts are closed and will
remain closed until the ‘RESET’ button is pressed.