EasyManua.ls Logo

Camus Hydronics DRH5000 - Page 29

Camus Hydronics DRH5000
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Figure 22: Lockout Condition
To eliminate the lockout error,
1) Press the red bar, indicating a Lockout condition
2) Press the [Lockouts] button
Figure 23: Lockout History
3) Press [Clear Lockout]
Table 13: Alert/Hold Codes
Description
29
Burner
s
witch turned OFF
30 Burner switch turned ON
47
Invalid subsystem reset request occurred
50 Modulation Fault (DR300 – 1000 ONLY)
61
Anti
-
short Cycle
62 Fan speed not proved
63
LCI off
, safety
circuit
is open
68 Setpoint was overridden due to sensor fault
69 Modulation was overridden due to sensor fault
123 Modulation rate was limited due to outlet limit
124 Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to
sensor failure
229 Lead lag slave communication timeout.
275-
281
LCI off, safety circuit is open
283 Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of
Ignition period
292
Abnormal Recycle: Flame was lost during Main
Flame
Establishing Period
293 Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-
310
+
Interlock Off, safety circuit is open
324,
374-
379
Hardware flame bias. Flame sensor wire needs to
be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460 LCI lost in run
550 Delta T inlet/outlet limit was exceeded
* If an internal hardware fault is detected contact Camus®
technical support for troubleshooting procedure.
+
The alarm LED and alarm contacts are closed and will
remain closed until the ‘RESET’ button is pressed.

Table of Contents

Related product manuals