EasyManua.ls Logo

Camus Hydronics Dynaforce Series - Page 54

Camus Hydronics Dynaforce Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
COMPONENT
FAILURE MODE
ANALYSIS
Flame Disappears
During a Run
Cycle
The Dynaforce® boiler was
running and flame signal suddenly
disappeared.
Lockout: 106, 107, 108, 109
• Verify that all air has been purged from gas line
• Verify that boiler is properly grounded
• Inspect flame sensor and associated wiring. Replace if
necessary
Check for flame sensor cracks in the insulator or continuity to
ground
Adjust the air proving switch. Turn counter-clockwise to reduce
sensitivity
Adjust the blocked flue switch. Turn clockwise to reduce
sensitivity
• Verify incoming gas supply pressure and that it coincides with
Table 7.
• Verify that the gas line connections to the boiler are adequate.
Refer to Table 6.
• Verify that the vent/ air inlet piping (if equipped) are correctly
installed and obstructions are not present
• Verify that 24 VAC is being supplied to the gas valve during
operation. If a signal cannot be detected, the transformer needs
to be replaced
• Inspect the burner. Refer to Burner Maintenance in section 10.5
• Replace the Dynaforce® Controller if necessary
Noisy Operation
• Supply Gas Issue
• Refer to Part 3 Gas Connection in this manual.
• Natural Gas Pressure reads between 3” w.c. and 14” w.c.
• L.P. Gas Pressure should be at 11” w.c.
• Air/Gas Mixture Issue
• Refer to Section 8.3 Gas Valve Adjustment Procedure for proper
combustion setting.
• Air Inlet and/or Vent configuration
• Refer to Part 2 Air Inlet and Venting
• Dirty/ Damaged Burner
• Refer to Burner Maintenance in section 10.5 of this manual for
the burner removal and inspection procedure. Clean or replace
the burner, if required.
Fan is vibrating
Check that all fan bolts are torqued to 20 lb-ft (DR300 1000),
25 lb-ft (DR1200 5000)
• Air in the piping system
• Purge all air from the piping system
Auto Reset High
Limit Trips
• The outlet temperature has
exceeded the set point
temperature specified.
Alert: 67, 79, 137, 303-310
ILK OFF
• Verify that the system is full of water and that all air has been
properly purged from the system.
• Verify that ∆T does not exceed 30
o
F across the heat exchanger
• Verify that the boiler is piped properly.
• Verify that 120VAC is being supplied to the boiler pump on a call
for heat. If voltage cannot be detected check wiring.
• Verify that the pump is circulating when 120VAC is detected. If
not, pump impeller may be stuck. Use a flat head screwdriver on
face of pump to turn impeller manually
• If 120VAC is present during a call for heat, but the pump still
does not circulate, replace the pump.
• Replace the main Dynaforce® Controller if necessary

Table of Contents

Related product manuals