EasyManua.ls Logo

Camus Hydronics Dynaforce Series - TROUBLESHOOTING; COMPONENT FAILURE ANALYSIS

Camus Hydronics Dynaforce Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
PART 9 TROUBLESHOOTING
COMPONENT
FAILURE MODE
ANALYSIS
Incoming Power
• Two wires interchanged
• No effect on safety
• Live and Neutral wires are interchanged.
Transformer
Tripped
The 24Volts and 120 Volts wired
are interchanged
Alert: 49
Lockout: 53
Breaker on transformer trips
Relief Valve
• System pressure exceeds relief
valve setting
• Replace the standard relief valve with a higher rated valve up to
the maximum pressure of the heat exchanger.
• Improperly sized expansion tank.
Flow Switch
• Flow Switch contacts are open
Alert: 63, 275-281, 460
LCI OFF
• Verify that pump is operating
• Verify for closed valves or obstructions in boiler piping
• Verify that all air has been purged from the system
• Verify that wiring is correct
Water Pressure
Switch
• Pressure Switch contacts are open
Alert: 63, 275-281, 460
LCI OFF
• Verify that minimum water pressure exceeds 30 PSI
• Verify that pump is operating
• Verify for closed valves or obstructions in boiler piping
• Verify that all air has been purged from the system
Verify that wiring is correct
Flame Failure
• The boiler has failed to ignite the
burner
Alert: 110, 291-294
To reset the module refer to section 5.8.2
• Verify that all air has been purged from gas line
Inspect hot surface igniter and related wiring for damage and
connection errors
DR 300 2500: Verify igniter is glowing
DR 3000 5000: Verify pilot is lit
• Inspect flame sensor and associated wiring. Replace if
necessary
• Verify that boiler is properly grounded
• Verify incoming gas supply pressure and that it coincides with
Table 7.
• Verify that the vent/ air inlet piping (if equipped) are correctly
installed and obstructions are not present.
• Verify 24 VAC (DR 300 1200) and 115VAC (DR 1400 5000)
is being supplied to the gas valve relay from the Dynaforce®
Controller during ignition. Check wiring from Dynaforce®
Controller and Gas Valve Relay. If a signal cannot be detected,
the Dynaforce® Controller needs to be replaced
If 24 VAC is present, check the outlet of the valve to ensure that
gas is flowing. When the valve is energized a change in
pressure should occur, if no change is detected the gas valve
has failed to open or it is passing insufficient amount of gas. If
this is an initial startup increase the low fire gas setting by ¼
turn clockwise.
• Inspect the burner. Refer to Burner Maintenance in section 10.5
• Replace the Dynaforce® Controller, if necessary

Table of Contents

Related product manuals