Gas Leakage Detector +0300047IE rel 1.1 - 26.04.2023
Maintenance
Remove the cylinder
by pressing the lever
and then detaching
the two parts.
Immerse the cylinder in a container  lled with tap water for a few seconds.
Place it back in the previous position
and close the  lter, as shown in the
gure.
Note the direction of
air fl ow (towards the sensor).
Assemble the various components as shown in the  gure, without connect-
ing the tube to the GLD.
Open the regulator on the gas cylinder to a pressure of around 0.5 l/min and
let the gas  ow for a few seconds without the calibration adapter connected
to the sensor, then connect the tube to the GLD.
Alternatively, to vent any residual air from the kit, before  xing the cap to the
sensor, let some gas  ow out for a few seconds.