25
“UE BASIC” +08C0042EZ - rel. 1.0 - 16.10.2017
ENG
Table of water circuit, electrical and electronic spare parts, UE025 to UE065
description spare part code pos. gure
UE025 UE035 UE045 UE065
Water circuit
Drain pump hose UEKDH00000 7 9.c
Manifold UEKCOLL000 6 9.c
Drain pump kit KITPSE0000 5 9.c
Internal tubing kit UEKT10000L UEKT1000XL 3 9.c
Double check valve kit FWHDCV0000 -
Conductivity meter kit KITCN00000 4 9.c
Fill solenoid valve kit KITVC10058
KITVC10070 2 9.c
Drain circuit UEKDC00000 UEKDC10000 1 9.c
Electrical and electronics
Display terminal HCTLEYFCw0
(3)
18 9.d
TAM (current transformer) UEKTAM0000 9 9.d
Contactor
UEKCONT200 URKCONT400 URKCONT300 10
Power transformer: 230/400-24V UEKTR30000 11 9.d
Electronic controller UEYxxvCz0i
(2)
14 9.d
Fuse carrier URKFH20000 13 9.d
Pump control relay UEKRD00000 -
F1 - F2 230 to 400Vac power fuses UEKFUSE100 UEKFUSE100 UEKFUSE100 UEKFUSE100 - see wiring diagrams
F3 Pump fuse URKFUSE300 - see wiring diagrams
F4 Transformer secondary fuse UEKFUSE400 - see wiring diagrams
Connection cable between
terminal and electronic controller
S90CONN002 -
Tab. 9.c
(1) when ordering, as well as the controller code specify the complete code and serial number of the humidier.
(2) xx: kg/h ( 01,......65) - v: power supply ( K=230V 3ph, L=400V 3ph, etc )
z: match digit board (8th code number of the card) - i: 0 single package / 1 multiple package
(3) w: match digit terminal (9th code number of the terminal)
Table of spare parts for standard and special cylinders UE025 to UE065
Description UE025 UE035 UE045 UE065
STANDARD openable cylinders 400V 3ph cylinder, conductivity 350 to 1250 µS/cm BLCT4D00W2 BLCT4D00W2 BLCT4C00W2 BLCT5C00W0
SPECIAL openable cylinders 400V 3ph cylinder, conductivity 75 to 350 µS/cm BLCT4C00W2 BLCT4C00W2 BLCT4B00W2 BLCT5B00W0
SPECIAL not openable cylinders 400V 3ph cylinder, conductivity 75 to 350 µS/cm BL0T4C00H2 BL0T4C00H2 BL0T4B00H2 BL0T5B00H0
400V 3ph cylinder, conductivity 350 to 1250 µS/cm BL0T4D00H2 BL0T4D00H2 BL0T4C00H2 BL0T5C00H0
Electrode and gasket kit 400V 3ph cylinder, conductivity 75 to 350 µS/cm KITBLCT4C2 KITBLCT4C2 KITBLCT4B2 KITBLCT5B0
400V 3ph cylinder, conductivity 350 to 1250 µS/cm KITBLCT4D2 KITBLCT4D2 KITBLCT4C2 KITBLCT5C0
Gasket and lter kit KITBLC4FG0 KITBLC4FG0 KITBLC4FG0 KITBLC5FG0
Tab. 9.d
9.3 Cleaning and maintenance of the cylinder
Replacement
Important: he cylinder must be only be replaced by qualied personnel, and with
the humidier unplugged from the power supply.
In normal conditions, the disposable cylinders should be replaced after one year (or
2500 hours of operation, if cleaned periodically), while the openable cylinders last 5 years
(or 10,000 hours of operation, if cleaned periodically). They must be replaced immediately
– even before the specied intervals – if any anomalies occur. For example, when the lime
scale inside the cylinder prevents the correct ow of electric current.
Replacement procedure:
1. empty all the water (see chap. 6);
2. turn o the humidier (switch “0”), and open the mains disconnect switch on the
power supply (safety procedure);
3. wait for the humidier and the cylinder to cool down;
4. remove the front cover;
5. disconnect the electrical cables from the cylinder;
6. release the cylinder from the locking device and lift it to remove it;
7. insert the new cylinder (make sure that the model and the power supply of the new
cylinder correspond to the rated data);
8. fasten the cylinder;
9. reconnect the electrical cables to the cylinder;
10. replace the front cover;
11. switch on the humidier;
12. reset cylinder operating hour counter (see parameters da , chap. 7);
13. Activate the wash new cylinder procedure, pressing ENTER + DOWN for 5 seconds
Periodical checks
After one hour of operation: check for any signicant water leaks.
Every 15 days or no more than 300 operating hours: check operation, the absence of
signicant water leaks, the general conditions of the casing. Check that during operation
there are no arcs or sparks between the electrodes.
Every 3 months or no more than 1000 operating hours: