3. STEAM DISTRIBUTION
3.1 CAREL jet distributors (SDPOEM00**)
These can be tted horizontally or vertically (hole facing upwards).
See page 48 for the models of distributors.
Assembly instructions (see Fig.3.a):
• make a series of holes on the wall according to the distributor drilling
template;
• insert the distributor;
• fasten the ange using 4 screws.
31,5 (1.2”)
50 (1.9”)
57,5(2.3”)
100 (3.9”)
C
C
A
B
A
B
50 (1.9”)
50 (1.9”)
31,5 (1.2”)
31,5 (1.2”)
31,5 (1.2”)
56(2.2”)
5(0.2”)
30 (1.2”)
22 (0.9”)
8(0.3”)
30 (1.2”)
22 (0.9”)
8(0.3”)
D
Fig. 3.a
Key:
A.
steam inlet
B.
condensate drain
C.
steam outlet.
the dimensions of the hole vary depending on the models of distributor:
model SDPOEM0022: diameter of the hole 22 mm (0.9”).
D
drilling template
Note: if steam hoses with an inside diameter of 30 mm (1.2”) are used,
remove the 22 mm (0.9”) steam inlet section.
3.2 CAREL linear distributors for air ducts
(DP***DRU)
Install away from obstacles (curves, branches, changes in cross-section, grills,
lters, fans). Minimum distance between the distributor and the obstacle:
1/1.5 m (3.3/4.9 ft). Increase the distance if:
• the air speed increases in the duct,
• the relative humidity of the air increases before and after humidi cation,
• the turbulence decreases.
See page 49 for installation examples.
Assembly instructions (see Fig.3.b):
• make a series of holes on the wall according to the distributor drilling
template (included in the packaging with the distributor);
• fasten the ange using 4 screws.
A 22 30 40
B 10 10 10
Y 58 68 89
35 45 60
X 68 77 99
dimensioni in mm
B
Y
X
A
X
°2
1
2
3
4
5
6
8
7
Fig. 3.b
Key:
1
“L”-shaped mounting support (where featured)
2
ange gasket
3
steam inlet (ØA)
4
condensate drain (ØB)
5
screw diameter (see the instruction sheet supplied with the distributor)
6
length (depending on the model of distributor, see par. “10.5” page 42)
7
angle (around 2°) for draining the condensate.
8
diameter of the hole on the wall (ØY)
Dimensions in mm (in)
CAREL linear distributors
DP***D22RU DP***D30RU DP***D40RU
ØA
22 (0.9”) 30 (1.18”) 40 (1.57”)
ØB
10 (0.4”) 10 (0.4”) 10 (0.4”)
ØY
58 (2.3”) 68 (2.7”) 89 (3.5”)
Ø
35 (1.4”) 45 (1.8”) 60 (2.4”)
X
68 (2.7”) 77 (3.0”) 99 (3.9”)
Tab. 3.a
Important:
1. t the distributor at a slight incline (at least 2°, to prevent the return of
condensate);
2. the “L”-shaped mounting support (see part 1 Fig. 3.c) is supplied with
steam distributor models from DP085* to DP025*. For shorter lengths,
the support can be supplied as an option (code 18C478A088).
3.3 CAREL steam blowers (VSDU0A*, models
UE001 to UE018 only)
Steam distributors for humidi ers with ow rates up to 18 kg/h (39.7 lb/h).
Can be connected on top of the humidi er, or separately in another location
(see the gure below).
A
B
C
D
E
F
G
DIMENSIONS
(m)/(feet)
AB CD
>0,5
(1.64)
>5
(16.4)
≥2,1
(6.9)
>1
(3.3)
DIMENSIONS
(m) /(feet)
EFG
>0,5
(1.64)
>5
(16.4)
>1
(3.3)
Fig. 3.c
Important:
For correct distribution of the steam, observe
For correct distribution of the steam, observe
the distance shown in the gure above.
3.4 Steam hoses
• use CAREL hoses (max. 4 m ( max. 13 feet)) long, see “Models of steam
hoses”, page 47). Rigid pipes may break and cause steam leaks;
• avoid the formation of pockets or traps (causes of condensate);
• avoid restricting the hose due to tight bends or twisting.
• fasten the end of the hose to the connectors on the humidi er and the
steam distributor using metal clamps, so that these do not detach due to
the high temperature.
• Avoid situations that cause stress on the outlet of the steam cylinder and
on the distributor pipe (see minimum diameter of curving).