18
ENG
“UEX-PLUS” +03U0040EN - Rel. 1.35 - 10.05.2013
installeruserservice
5. REMOTE TERMINAL AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidi er and moved to
another place.
Depending on the distance required, the following are necessary:
• up to 50 meters ( 164 feet ): 6-wire telephone cable and two EMC lters
(code 0907858AXX) (see Fig. 5.a);
• up to 200 meters: two CAREL TCONN6J000 boards, 6-wire telephone
cables and an AWG20-22 shielded cable with 3 twisted pairs (for the
connection of the two boards, Fig. 5.b).
Note: to ll the empty space left by the display terminal on the
humidi er, use CAREL kit code HCTREW0000.
Remote connection of the terminal up to max 50 m ( 164 feet )
J18
humiSteam
3
2
1
2
Fig. 5.a
Key:
1
telephone cable (up to 50 m
( 164 feet ) distance);
2
EMC lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Remote connection of the terminal up to 200 m ( 656.1 feet )
J18
humiSteam
4
2
2
A
J14
1 2 3 1 2 3
J15
B
C
SC
A
J14
1 2 3 1 2 3
J15
B
C
SC
5
3
3
1
Fig. 5.b
Key:
1
telephone cable (up to 0.8 m
( 2.6 feet ) distance);
2 CAREL TCONN6J000 board;
3 pin strip J14 and J15 in position 1-2 (power supply available on the
telephone connectors A, B and C and screw SC);
4
WG20-22 shielded cable with 3 twisted pairs to move the display
terminal up to 200 m away. Connection to the TCONN6J00 board:
terminal SC function
0 EARTH (shield)
1 +VRL
2 GND
3 RX/TX-
4 RX/TX+
5 GND
6 +VRL
5 remote display terminal
5.2 Supervisory network (J19)
The humidi er is equipped serial interface of the following:
• PCOS004850 (for connections protocol Carel, Modbus®, Winload).
Instead of the supplied, they can be connected to a supervisory system
via RS232 serial lines or FTT10 LON using the optional cards shown in the
following table.
optional cards characteristics supported protocols
PCO100UWBK Provides BACnet™ 8802.3 Ethernet,
BACnet™/IP and MS/TP connectivity
BACnet™
PCO100UBAK Provides BACnet MS/TP over RS485
BACnet™
BACnet™
PCO1UX00F0 Used to interface of the controller
to an FTT10 LON network, when
suitably programmed
LON-Echelon®
Connection is also possible to TREND systems using a card sold directly by
TREND ( website: http://www.trendcomms.com ).
+ -
GND
connection terminal block
for RS-485 board
Fig. 5.c (detail of the electronic board, humidifi er electrical compartment)
For the connecting remove the cover , and connect cards optional connector
J19.