5. REMOTE TERMINAL AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidi er and moved to
another place.
Depending on the distance required, the following are necessary:
up to 50 meters ( 164 feet ): 6-wire telephone cable and two EMC  lters
(code 0907858AXX) (see Fig. 5.a);
up to 200 meters: two CAREL TCONN6J000 boards, 6-wire telephone
cables and an AWG20-22 shielded cable with 3 twisted pairs (for the
connection of the two boards, Fig. 5.b).
Note: to  ll the empty space left by the display terminal on the
humidi er, use CAREL kit code HCTREW0000.
Remote connection of the terminal up to max 50 m ( 164 feet )
J18
humiSteam
3
2
1
2
Fig. 5.a
Key:
1
telephone cable (up to 50 m
( 164 feet ) distance);
2
EMC  lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Remote connection of the terminal up to 200 m ( 656.1 feet )
J18
humiSteam
4
2
2
A
J14
1 2 3 1 2 3
J15
B
C
SC
A
J14
1 2 3 1 2 3
J15
B
C
SC
5
3
3
1
Fig. 5.b
Key:
1
telephone cable (up to 0.8 m
( 2.6 feet ) distance);
2 CAREL TCONN6J000 board;
3 pin strip J14 and J15 in position 1-2 (power supply available on the
telephone connectors A, B and C and screw SC);
4
WG20-22 shielded cable with 3 twisted pairs to move the display
terminal up to 200 m away. Connection to the TCONN6J00 board:
terminal SC function
0 EARTH (shield)
1 +VRL
2 GND
3 RX/TX-
4 RX/TX+
5 GND
6 +VRL
5 remote display terminal
5.2 Supervisory network (J19)
The humidi er is equipped serial interface of the following:
PCOS004850 (for connections protocol Carel, Modbus®, Winload).
Instead of the supplied, they can be connected to a supervisory system
via RS232 serial lines or FTT10 LON using the optional cards shown in the
following table.
optional cards characteristics supported protocols
PCO100UWBK Provides BACnet™ 8802.3 Ethernet,
BACnet™/IP and MS/TP connectivity
BACnet™
PCO100UBAK Provides BACnet MS/TP over RS485
BACnet™
BACnet™
PCO1UX00F0 Used to interface of the controller
to an FTT10 LON network, when
suitably programmed
LON-Echelon®
Connection is also possible to TREND systems using a card sold directly by
TREND ( website: http://www.trendcomms.com ).
+ -
GND
connection terminal block
for RS-485 board
Fig. 5.c (detail of the electronic board, humidifi er electrical compartment)
For the connecting remove the cover , and connect cards optional connector
J19.