Cod. Parameter Status
c1 Minimum time between successive starts of the second compressor
NOTE: only active for AUX if H1 =12
Standard
c2 Minimum second compressor OFF time
NOTE: only active for AUX if H1 =12
Standard
c3 Minimum second compressor ON time
NOTE: only active for AUX if H1 =12
Standard
c11 Second compressor start delay if H1 = 7 no temp. control of AUX compressor
Standard
Tab. 3.j
3.12 Pump down
The pump down function can be activated when the parameter H1 = 5 and c7 ≥ 7.
The AUX relay is then dedicated to the pump down valve.
Digital input DI1 has to be congured as a low pressure switch A4 = 8 or pump down will be performed by
time if c10 = 1.
To start with pump down, control of the Fullmotion compressor needs to stop, then pump down starts. An
immediate pump down can be performed by setting cct = 0.
If c10 = 1 and no pressure switch is congured (A4 = 8) the pump down lasts for the time c7.
The compressor start can be delayed by the time c8.
Cod. Parameter UOM Dis. Type Def. Max Min
c7 Maximum pump down time (PD)
0 = Pump down disabled
Sec C I 0 900 0
c8 Compressor start delay after opening PD valve
Sec C I 5 60 0
c9 Autostart in pump down
0 = Disabled
1 = Pump down whenever closing pump down valve &
following low pressure switch activation with no cooling
demand
- C 1 1 0
c10 Pump down by time or pressure
0 = pressure
1 = time
- C D 0 1 0
A4 Digital input 1 conguration (DI1)
8 = low pressure switch
min C 0 1 0
H1 Congure function of output AUX1
5 = pump down valve
7 = delayed compressor (see c11)
11 = reverse with neutral zone
12 = second compressor
13 = no function
14 = drain heater management
- C I 14 14 0
Tab. 3.k
3.13 OFF from keypad
Pressing the ON/OFF button for more than 3 seconds switches the controller ON/OFF.
If speed control is running, the Fullmotion compressor is forced to run at the minimum speed set by cmf for
a xed time of 30 sec.
If the controller is congured for pump down, the controller activates pump down management.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel ir33+ FMC and is the answer not in the manual?

Carel ir33+ FMC Specifications

General IconGeneral
BrandCarel
Modelir33+ FMC
CategoryController
LanguageEnglish

Related product manuals