91
ENG
µchiller +0300053EN rel. 2.2 - 14.12.2021
Supervisor table
7. SUPERVISOR TABLE
Chiller provides a database of supervisor variables via Modbus RTU protocol over RS485 (BMS port on the Chiller controller).
The BMS port has the following default settings:
• baud rate 115,200;
• data bits 8;
• no parity;
• stop bits 1.
See "Parameter table: BMS port" to set diff erent values.
"Index" is the address specifi ed in the Modbus® frame.
7.1 Coil Status
Index Size Ref. Type Min/Max R/W UoM Description
0 1 U001 BOOL R/W U001 - Reset user pump 1 hour counter
1 1 U004 BOOL R/W U004 - Reset user pump 2 hour counter
2 1 U010 BOOL R/W U010 - Enable set point compensation (0 = Disabled, 1 = Enabled)
3 1 U017 BOOL R/W U017 - Enable scheduler (0 = disabled, 1 = enabled)
4 1 U022 BOOL R/W U022 - Scheduler type (0 = Switch off , 1 = Change set point)
5 1 U034 BOOL R/W U034 - Type of cooling/heating changeover (0 = Keypad, 1 = DIn)
6 1 U036 BOOL R/W U036 - Control probe at start-up (0 = Return, 1 = Delivery)
7 1 U038 BOOL R/W U038 - Control probe when running (0 = Return, 1 = Delivery)
8 1 U057 BOOL R/W U057 - Remote alarm input logic (0 = NC, 1 = NO)
9 1 U058 BOOL R/W U058 - Cooling/heating input logic (0 = NO, 1 = NC)
10 1 U059 BOOL R/W U059 - Remote unit ON/OFF input logic (0 = NO, 1 = NC)
11 1 U060 BOOL R/W U060 - User pump fl ow input logic (0 = NC, 1 = NO)
12 1 U061 BOOL R/W U061 - User pump overload input logic (0 = NC, 1 = NO)
13 1 U062 BOOL R/W U062 - 2nd set point input logic (0 = NO, 1 = NC)
14 1 U063 BOOL R/W U063 - User pump output logic (0 = NC, 1 = NO)
15 1 U064 BOOL R/W U064 - Global alarm relay output logic (0 = NC, 1 = NO)
16 1 U065 BOOL R/W U065 - Free cooling valve output logic (0 = NO, 1 = NC)
17 1 U066 BOOL R/W U066 - Frost protection heater output logic (0 = NC, 1 = NO)
18 1 U067 BOOL R/W U067 - Alarm relay confi guration (0 = Contrlo alarms, 1 = All alarms)
19 1 U068 BOOL R/W U068 - Enable free cooling (0 = disabled, 1 = enabled)
20 1 E000 BOOL R/W E000 - ExV circ. 1 enable manual mode
21 1 E002 BOOL R/W E002 - ExV circ. 2 enable manual mode
22 1 Hd06 BOOL R/W Hd06 - Enable power supply request from BMS (0 = Disabled, 1 = Enabled)
23 1 C001 BOOL R/W C001 - Comp. 1 circ. 1 reset hour counter
24 1 C004 BOOL R/W C004 - Comp. 2 circ.1 reset hour counter
25 1 C007 BOOL R/W C007 - Comp. 1 circ. 2 reset hour counter
26 1 C010 BOOL R/W C010 - Comp. 2 circ. 2 reset hour counter
27 1 C034 BOOL R/W C034 - High pressure switch input logic (0 = NC, 1 = NO)
28 1 C035 BOOL R/W C035 - Comp. overload input logic (0 = NC, 1 = NO)
29 1 C036 BOOL R/W C036 - Comp. output logic (0 = NO, 1 = NC)
30 1 C044 BOOL R/W C044 - Enable circuit destabilisation (0 = Disabled, 1 = Enabled)
31 1 S001 BOOL R/W S001 - Source pump 1 reset hour counter
33 1 S009 BOOL R/W S009 - Source fan 1 circ. 1 reset hour counter
34 1 S013 BOOL R/W S013 - Source fan 1 circ. 2 reset hour counter
35 1 S020 BOOL R/W S020 - Enable low noise (0 = Disabled, 1 = Enabled)
37 1 S043 BOOL R/W S043 - Enable sliding defrost (0 = Disabled, 1 = Enabled)
38 1 S055 BOOL R/W S055 - Comp. behaviour after defrosting
(0 = Comp. OFF, 1 = Comp. ON)
39 1 S061 BOOL R/W S061 - Source fan output logic (0 = NC, 1 = NO)
40 1 S062 BOOL R/W S062 - Source pump output logic (0 = NC, 1 = NO)
41 1 S063 BOOL R/W S063 - Reversing valve output logic (0 = NC, 1 = NO)
42 1 S064 BOOL R/W S064 - Source fl ow type (0 = Independent, 1 = Common)
44 1 S065 BOOL R/W S065 - Source fan type (0 = Inverter, 1 = ON/OFF)
46 1 S068 BOOL R/W S068 - Source type (0 = Air, 1 = Water)
47 1 UoM BOOL R/W UM - Unit of measure used for 2-row display and BMS, not Applica
(0 = ° C / bar, 1 = ° F / PSI)
48 1 Hc02 BOOL R/W Hc02 - Enable analogue channel 4 (0 = Disabled, 1 = Enabled)
49 1 Hc12 BOOL R/W Hc12 - Digital output 6 confi g. (0 = Frost protection, 1 = Source fan / Source pump)
50 1 Hc13 BOOL R/W Hc13 - Enable buzzer (0 = Disabled, 1 = Enabled)
52 1 Ha02 BOOL R/W Ha02 - Set controller internal clock (0 = No setting, 1 = Set)
53 1 Hd03 BOOL R/W Hd03 - Enable NFC (0 = disabled, 1 = enabled)
54 1 UnSt BOOL R/W UnSt - Unit ON/OFF command from keypad (0=OFF 1=ON)
55 1 ModE BOOL R/W ModE - Cool/Heat mode from keypad (0 = Cool, 1 = Heat)
56 1 RES BOOL R/W RES - Reset active alarms from BMS net (0 = NO, 1 = Reset)
59 1 ClrH BOOL R/W ClrH - Delete alarm log (0 = No, 1 = Yes)
63 1 Hd05 BOOL R/W Hd05 - Enable unit ON/OFF command from BMS net (0 = Disabled, 1 = Enabled)