1.4 Steam distribution
1.4.1A Duct injection
NOTE: If the ventilated steam distributor is to be used, then go to section 1.4.1B.
Each unit has either 7/8” (22 mm), 1-1/4” (30 mm) diameter outlet or 1-5/8 (40 mm) diameter outlets. Some
units have multiple outlets. The duct distributors and steam hose must be matched in size to the diameter of
the steam outlets for the units:
UNIT MODEL NUMBER
UE001 UE003 UE005 UE008 UE009 UE010 UE015 UE025 UE035 UE045 UE065
No.
Cylinders 1
Steam
outlets 22mm x 1 30mm x 1 40mm x 1 40mm x 2
Duct steam distributors must also be matched to the duct size they will be inserted into:
Quantity Required per Unit
Humidifier Steam Outlet s, mm
22 30 40 2x40
Humidifier Steam Outlet s, in ches
7/8 1-1/4 1-5/8 2x1-5/8
Nominal Duct Size, In ches
Distributor Length, Inches
Ordering
Code
Description
UE 001,003
UE 005,008,009,010,015
UE 025,035,045HM,045HN
UE 045HW,045HK,065
22 mm Duct Distributors:
12 11.9 DP030D 22RU
Duct steam distributor, 22mm, 12'', 20 l bs/hr
1
18 17.8 DP045D 22R0
Duct steam distributor, 22mm, 18'', 20 l bs/hr
1
24 23.7 DP060D 22R0
Duct steam distributor, 22mm, 24'', 20 l bs/hr
1
36 33.5 DP085D 22R0
Duct steam distributor, 22mm, 36'', 20 l bs/hr
1
30 mm Duct Distributors:
12 11.9 DP030D 30RU
Duct steam distributor, 30mm, 12'', 33 l bs/hr
1
18 17.8 DP045D 30RU
Duct steam distributor, 30mm, 18'', 42 l bs/hr
1
24 23.7 DP060D 30RU
Duct steam distributor, 30mm, 24'', 42 l bs/hr
1
36 33.5 DP085D 30R0
Duct steam distributor, 30mm, 36'', 47 l bs/hr
1
48 41.4 DP105D 30R0
Duct steam distributor, 30mm, 48'', 47 l bs/hr
1
60 49.3 DP125D 30R0
Duct steam distributor, 30mm, 60'', 47 l bs/hr
1
72 65 DP165D 30RU
Duct steam distributor, 30mm, 72'', 47 l bs/hr
1
40 mm Duct Distributors:
24 23.7 DP060D 40RU
Duct steam distributor, 40mm, 24'', 99 l bs/hr
1 2
36 33.5 DP085D 40R0
Duct steam distributor, 40mm, 36'', 103 lbs/hr
1 2
48 41.4 DP105D 40R0
Duct steam distributor, 40mm, 48'', 103 lbs/hr
1 2
60 49.3 DP125D 40R0
Duct steam distributor, 40mm, 60'', 103 lbs/hr
1 2
72 65 DP165D 40R0
Duct steam distributor, 40mm, 72'', 103 lbs/hr
1 2
84 80.8 DP205D 40R0
Duct steam distributor, 40mm, 84'', 103 lbs/hr
1 2