1 Installation
1.1 Positioning
The HumiSteam has been designed for wall mounting
(although it can be placed on a stand) and, since it is an
atmospheric steam humidifier, should be placed close to
the point where the steam will be used, to minimize the
steam hose length (and condensate). Certain clearances
must be maintained around the unit:
A B C D E F
Minimum
Dimension
(inches)
12
8 8 16
28
<0.5°
With room blow er units, other clearances are
needed:
Unit Dimensions:
* = UE045 for 460-575/3 Vac
** = UE045 for 208-230/3 Vac
VSDU0A
A B C D E F H
20 72 72 24 20 72 24
VRDXL
Minimum
dimension
(inches)
36 120
72 48 36 120
48
Model - UE
001-008 009-015 025-045* 045**-065
A
15 15 22 26
B
11 11 15 18
Dimensions
(inches)
C
25 28 35 38
packaged
36 44 86 113
empty
30 38 75 97
Weight
(lbs)
installed
42 60 134 207