Parameters for setting the serial connections and remote control:
Code
Range Unit Description
C0
1 to 6 1 Value normally displayed
1= room sensor measurement
2= outlet sensor measurement
3= steam output
4= hour counter
5= conductivity
6= current
Enable keypad and remote control - keypad: remote control:
0= read of all param., (modify C1 only) read and modify param. P, d and St
1= read and modifiy all parameters read and modify param. P, d and St
2= read of all param., (modify C1 only) read parameters P, d and St
3= read and modify all parameters read parameters P, d and St
C1
0 to 4 4
4= read and modify all parameters read and modify all parameters
C2
0 to 99 0 Remote control enabling code (see paragraph 8.2)
C3
0 to 199
1 Serial address
C4
0 to 3 3 Supervisor: baud-rate 0=1200, 1=2400, 2=4800, 3=9600
Supervisor: frame (character bits, parity, stop bits)
0=8,N.2 6=7,N.2
1=8,N,1 7=7,N,1
2=8,E.2 8=7,E.2
3=8,E,1 9=7,E,1
4=8,O.2 10=7,O,2
C5
0 to 11 0
5=8,O,1 11=7,O,1
C6
0 to 199
0 Ms serial reply send delay
0=terminal
1=terminal with ON/OFF control
2=term. with ON/OFF and room sensor
C7
0 to 3 0
Graphic terminal configuration in cases 1,2,3
the OFF command is forced on start-up
3=term. with ON/OFF and hi-limit
sensor
3.5 Notes about special parameters
b1, setting 2 : Drain under power
If parameter b1 includes setting 2, the humidifier will continue to produce steam during drain cycles. If this
setting is turned off, the humidifier will open the power contactor during drain cycles.
b1, setting 4 : Draining due to a significant reduction in the demand
If parameter b1 includes setting 4, then the humidifier will not drain if the demand for humidification decreases.
This helps to conserve conductivity and is useful in low conductivity waters. If b1, setting 4 is off, then the
humidifier will drain to reduce the output if the demand is reduced by 33%.
b1, setting 8 : Automatic draining of the cylinder after period of non-use
If parameter b1 includes setting 8, parameter “bF” may be used to cause the humidifier to empty the steam
cylinder if there has been no demand for humidification for an extended period of time. This helps prevent
premature corrosion of the electrodes and/or contamination of the water in the cylinder. The default setting is
for 3 days. The unit will display idr” when this drain function occurs.
b1, setting 64 : Complete periodic draining
If parameter b1 includes setting 64, then parameter “bE can be used to set the hours between total drains of
the cylinder. This is useful if the water contains impurities that can cause erratic behavior.