DEFROST PACKAGE – DEFR201
The optional defrost timer allows the chamber to operate at low temperatures down to 0°C. When
operating the chamber with this option, it is recommended to utilize the defrost system to prevent
ice build-up on the condensing coil. The defrost time is pre-set to provide four defrost cycles
every 24 hours (once every 6 hours) with the defrost duration at 16 minutes. While the unit is in
the defrost mode, the temperature may drift up a couple degrees. To adjust timer settings remove
top cover of unit. Timer located in front right hand corner of unit.