EasyManua.ls Logo

Carrier 30AWH006HB - 6.4.1 Resistance Values of Main Components

Carrier 30AWH006HB
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
30AW
Diagnostic
6
6.4.1 Resistance values of main components
4 6 8 12 15
T ref
[°C]
T ref
[°C]
T ref
[°C]
T ref
[°C]
T ref
[°C]
PMV 46±4 25 46±4 25 46±4 20 46±3 20 46±3 20
4 Way 1795±150 25 1795±150 25 1765±150 24 1774±150 24 1489±150 22
Fan
motor
22±2 25 22±2 25 22.4±2 24 35.2±2 24 17.9±2 22
21.9±2 25 21.9±2 25 22.6±2 24 34.8±2 24 18.9±2 22
21.9±2 25 21.9±2 25 22.6±2 24 35±2 24 17.7±2 22
HP size: 4-6-8 kW V1 V2 V3
Pump: NYL 63-15 Main 246.1±20 177.4±20 108.8±10
Aux 137.8±10 137.8±10 137.8±10
T ref [°C] 23 23 23 °C
HP size: 12-15 kW V1 V2 V3
Pump: SXM 25-60 Main 144.7±15 107.3±10 70.9±7
Aux 72.8±7 72.8±7 72.8±7
T ref [°C] 23 23 23 °C
SM_30AW.indd 89 14-03-2011 14:45:44