57
30AW
Control management
5
When power supply is reset
Fail Mode
Anti Freeze Protection in O Mode
When a unit is powered up, depending on its Auto Start conguration, it will start up with its last operating parameters, or
OFF Mode.
The EEPROM is available for saving the operating environment of the control in the event of a power-reset condition. If not
congured for auto start, at the power up the system will remain in OFF Mode.
All the NUI codes will be restored on a power up condition.
When the unit has a diagnostic failure, fail mode is executed.
*GUIF0QFSBUJOH.PEFJT'"*-UIFOUIFPOCPBSE-&%XJMMCMJOLUIFGBVMUDPEFTFOEUIF'PSDFE0òNFTTBHFUPUIF6OJUJO
case of not recoverable error and Water pump remains energized. In addition and if connected, the same message code
will be sent to NUI and, as an alternative, the alarm relay output should be activated as dened.
5IJTBMHPSJUINQSPUFDUTUIFSPPNGSPNGSFF[JOHXIFOJO0ò.PEFBOEJGTFMFDUFECZUIF6TFS)0.&"/5*'3&&;&FOBCMFE
that can also select the Antifreeze Temperature. An hysteresis of - 0°C /+2°C should be applied.
AF: Anti-
Freeze
NUI Code 2
HOME
ANTIFREEZE
AF
STATUS
CHILLER
UNIT: OFF
WP: OFF after
35 sec. if
was ON
NUI: OFF
Mode: ON Heat
WSP: 35°C
WP: ON
NUI: Display Antifreeze
CHILLER UNIT: OFF
WP: OFF after 30 sec. if
was ON
NUI: OFF + Antifreeze
START
Disable
enable
T< AF ValueT AF Value
<