The 30HXC 080-375 units for high condensing temperatures 
are directly derived from the standard models. Their appli-
cation range is the same as that of the standard units, but 
permits operation at condenser leaving water temperatures 
up to 63°C. The PRO-DIALOG control offers all the advan-
tages of the standard units, plus control of the condenser 
leaving water temperature.
The main modifications are:
•  Use of 30GX compressors (example: 06NA2300S5N 
instead of 06NW 2300S5N).
•  Modification of electrical components to operate with 
compressors for high condensing temperatures.
•  Modification of heat exchangers to meet pressure code 
requirements (if necessary).
Option 150
These units are designed for traditional applications for 
water-cooled units, but for higher condender leaving water 
temperatures than 50°C.
Like the standard units they are equipped with condenser 
entering and leaving water sensors.
It is possible to control the machine at the condenser water 
outlet, requiring a factory configuration change and the 
use of a heating/cooling inlet reversing device.
Option 150A
These units are designed for water-to-water heat pumps.
They are factory configured as heat pumps (heating/cooling 
control as a function of the remote reversing device). The 
condenser incorporates thermal insulation that is identical 
to that of the evaporator.
Technical information
All information is identical to that of the standard 30HXC 
units, except for the following paragraphs.
Selection
There are no nominal conditions for this unit type. The 
selection is made using the current electronic catalogue.
Dimensions
These are identical to those of the standard 30HXC units. 
The only difference is in the diameter of the incoming field 
wiring connection, described in the chapter “Recommended 
selection”. Refer to the dimensional drawings for these 
units, before proceeding with the wiring.
Compressor
See table in chapter 5.3.
Options and accessories
All options available for the standard 30HXC units are com-
patible, except low-temperature option 5 for the evaporator 
available in the special unit.
ATTENTION:  If units have two different operating modes 
- one with high condensing temperature and the other with 
low condensing temperature - and the transition is made 
with the unit in operation, the temperature must not vary 
by more than 3 K per minute. In cases where this is not 
possible, it is recommended to go through a unit start/stop 
switch (remote start/stop available for standard units).
The 30HXC units with the very low temperature option 
are directly derived from the 30HXC models equipped 
with the high condensing temperature option (option 150). 
Unit sizes available with the very low temperature option 
are the following: 30HXC 090, 110, 130, 155, 175, 200, 230, 
260, 310, 345.
Their application range allows the production of glycol/
water solution down to -10°C with ethylene glycol at 35% 
(by weight) or down to -7°C with propylene glycol at 30% 
(by weight). The precision of these amounts is critical for 
correct unit operation.
In addition to the ones already listed for the high condensing 
temperature option (see chapter 4.4) the main modifications 
are:
•  the evaporator is equipped with reinforced thermal 
38 mm insulation,
•  the electronic expansion valves are changed,
•  the use of a wide-band oil differential sensor.
All technical data is the same as for the 30HXC units with 
option 150 except for the following chapters:
4.5.1 - Options and accessories
The options available for the 30HXC units equipped with 
the very low temperature option are as follows: 20, 22, 60, 
61, 84, 84D, 84R, 92, 104A, 107, 107A, 152, 193, 194, 197, 199.
4.5.2 - Operating range, 30HXC units with very low 
temperature option
   
Evaporator entering water temperature  -7.2 21
Evaporator leaving water temperature -10 15
Evaporator entering water temperature -4.2 21
Evaporator leaving water temperature -7 15
Condenser entering water temperature 20 50
Condenser leaving water temperature 25 55
Outdoor air temperature 6 40
For very low temperature applications the anti-freeze 
solution is critical for correct unit operation. The following 
amounts (by weight) are required:
  
 25 27
 28 30
 30 NA
 33 NA
 35 NA