4
Prior to the initial start-up of the 30HXC/GX units, the 
people involved in the on-site installation, start-up, operation 
and maintenance of this unit should be thoroughly familiar 
with these instructions and the specific project data for the 
installation site.
The 30HXC/GX liquid chillers are designed to provide a 
very high level of safety during installation, start-up, opera-
tion and maintenance. They will provide safe and reliable 
service when operated within their application range.
This manual provides the necessary information to fami-
liarize yourself with the control system before performing 
start-up procedures. The procedures in this manual are 
arranged in the sequence required for machine installation, 
start-up, operation and maintenance.
Be sure you understand and follow the procedures and 
safety precautions contained in the instructions supplied 
with the machine, as well as those listed in this guide.
To find out, if these products comply with European 
directives (machine safety, low voltage, electromagnetic 
compatibility, equipment under pressure etc.) check the 
declarations of conformity for these products.
After the unit has been received, when it is ready to be 
installed or reinstalled, and before it is started up, it must be 
inspected for damage. Check that the refrigerant circuit(s) 
is (are) intact, especially that no components or pipes have 
shifted (e.g. following a shock). If in doubt, carry out a leak 
tightness check and verify with the manufacturer that the 
circuit integrity has not been impaired. If damage is detected 
upon receipt, immediately file a claim with the shipping 
company.
Do not remove the skid or the packaging until the unit is 
in its final position. These units can be moved with a fork 
lift truck, as long as the forks are positioned in the right 
place and direction on the unit.
The units can also be lifted with slings, using only the 
designated lifting points marked on the unit.
These units are not designed to be lifted from above. Use 
slings with the correct capacity, and always follow the 
lifting instructions on the certified drawings supplied with 
the unit. 
Safety is only guaranteed, if these instructions are carefully 
followed. If this is not the case, there is a risk of material 
deterioration and injuries to personnel. 
Never cover any safety devices.
This applies to the relief valve in the water circuit and the 
relief valve(s) in the refrigerant circuit(s).
Ensure that the valves are correctly installed, before 
operating the unit.
In certain cases the relief valves are installed on isolating 
valves. These valves are factory-supplied lead-sealed in the 
open position. This system permits isolation and removal 
of the relief valves for checking and replacing. The relief 
valves are designed and installed to ensure protection 
against overpressure caused by fire.
All factory-installed relief valves are lead-sealed to prevent 
any calibration change. If the relief valves are installed on 
a change-over manifold, this is equipped with a relief valve 
on each of the two outlets. Only one of the two relief valves 
is in operation, the other one is isolated. Never leave the 
change-over valve in the intermediate position, i.e. with both 
ways open (locate the control element in the stop position). 
If a relief valve is removed for checking or replacement 
please ensure that there is always an active relief valve on 
each of the change-over valves installed in the unit.
The safety valves must be connected to discharge pipes. 
These pipes must be installed in a way that ensures that 
people and property are not exposed to refrigerant leaks. 
These fluids may be diffused in the air, but far away from 
any building air intake, or they must be discharged in a 
quantity that is appropriate for a suitably absorbing 
environment.
Periodic check of the relief valves: See paragraph ‘Mainte-
nance safety considerations’.
Provide a drain in the discharge circuit, close to each 
relief valve, to avoid an accumulation of condensate or 
rain water. 
Ensure good ventilation, as accumulation of refrigerant in 
an enclosed space can displace oxygen and cause asphyxia-
tion or explosions.
Inhalation of high concentrations of vapour is harmful and 
may cause heart irregularities, unconsciousness, or death. 
Vapour is heavier than air and reduces the amount of oxy-
gen available for breathing. These products cause eye and 
skin irritation. Decomposition products are hazardous.
These products incorporate equipment or components under 
pressure, manufactured by Carrier or other manufacturers. 
We recommend that you consult your appropriate national 
trade association or the owner of the equipment or compo-
nents under pressure (declaration, re-qualification, retesting, 
etc.). The characteristics of this equipment/these components 
are given on the nameplate or in the required documenta-
tion, supplied with the products.
Engineers working on the electric or refrigeration compo-
nents must be authorized, trained and fully qualified to do so.
All refrigerant circuit repairs must be carried out by a trained 
person, fully qualified to work on these units. He must have 
been trained and be familiar with the equipment and the 
installation. All welding operations must be carried out by 
qualified specialists.