24
PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
38QRR030 / 40QAQ036
Te m p ° F ( ° C ) A i r
Entering
Condenser (Edb)
A i r E n t e r i n g E v a p o r a t o r --- C f m / B F
640/0.02 740/0.02 840/0.03
A i r E n t e r i n g E v a p o r a t o r --- E w b ° F ( ° C )
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 26.4 29.0 31.1 32.5 28.0 29.9 31.7 32.9 29.3 30.5 32.1 33.1
SHG 26.4 23.7 20.4 16.7 28.0 25.8 21.5 17.2 29.3 27.4 22.3 17.5
TC 25.7 28.2 30.4 31.8 27.3 29.2 31.0 32.1 28.6 29.8 31.3 32.4
kW 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59
CMP 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24
LDB 42.7 46.9 52.0 57.7 46.7 49.7 55.2 60.7 49.9 52.2 57.8 63.0
LWB 40.2 45.3 50.9 57.1 42.2 47.8 53.6 59.7 43.8 49.7 55.5 61.5
65
(18.3)
TCG 25.4 28.0 30.6 32.6 27.1 29.0 31.4 33.1 28.5 29.7 32.0 33.4
SHG 25.4 23.1 20.3 16.8 27.1 25.3 21.7 17.4 28.5 27.2 22.8 17.9
TC 24.7 27.2 29.8 31.8 26.4 28.2 30.7 32.3 27.8 29.0 31.2 32.6
kW 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75
CMP 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40
LDB 44.1 47.8 52.2 57.5 47.7 50.2 55.0 60.4 50.7 52.3 57.2 62.6
LWB 40.9 46.0 51.3 57.1 42.8 48.3 53.7 59.6 44.3 50.1 55.5 61.4
75
(23.9)
TCG 24.5 26.8 29.5 32.0 26.1 27.7 30.4 32.7 27.5 28.5 31.1 33.1
SHG 24.5 22.4 19.7 16.6 26.1 24.6 21.3 17.4 27.5 26.6 22.7 18.0
TC 23.8 26.0 28.7 31.2 25.4 27.0 29.7 31.9 26.7 27.7 30.4 32.4
kW 1.92 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93
CMP 1.57 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58
LDB 45.4 48.8 53.0 57.8 49.0 51.1 55.4 60.5 51.8 52.9 57.3 62.5
LWB 41.6 46.8 51.9 57.4 43.4 49.0 54.2 59.8 44.8 50.7 55.9 61.5
85
(29.4)
TCG 23.5 25.4 28.2 30.9 25.1 26.3 29.1 31.7 26.3 27.0 29.8 32.3
SHG 23.5 21.7 19.0 16.2 25.1 23.8 20.7 17.1 26.3 25.7 22.3 17.9
TC 22.8 24.7 27.4 30.2 24.3 25.6 28.4 31.0 25.6 26.3 29.1 31.5
kW 2.11 2.12 2.13 2.13 2.12 2.12 2.13 2.13 2.12 2.13 2.13 2.13
CMP 1.76 1.77 1.78 1.78 1.77 1.77 1.78 1.78 1.77 1.78 1.78 1.78
LDB 46.8 49.7 53.9 58.4 50.3 52.0 56.1 60.8 53.1 53.9 57.8 62.6
LWB 42.3 47.7 52.7 58.0 44.0 49.8 54.8 60.2 45.4 51.3 56.4 61.8
95
(35)
TCG 22.4 23.9 26.6 29.5 23.9 24.8 27.5 30.4 25.1 25.5 28.7 31.0
SHG 22.4 21.0 18.3 15.6 23.9 23.0 19.9 16.6 25.1 24.9 22.0 17.5
TC 21.7 23.2 25.8 28.8 23.1 24.0 26.7 29.7 24.3 24.7 28.0 30.3
kW 2.46 2.47 2.49 2.50 2.47 2.48 2.50 2.50 2.48 2.48 2.50 2.51
CMP 2.11 2.12 2.14 2.15 2.12 2.13 2.15 2.15 2.13 2.13 2.15 2.16
LDB 48.5 50.8 55.0 59.3 51.7 52.9 57.1 61.3 54.4 54.7 58.5 63.0
LWB 43.1 48.7 53.7 58.8 44.8 50.6 55.6 60.8 46.0 52.0 57.1 62.2
105
(40.6)
TCG 21.2 22.3 24.9 27.7 22.6 23.1 25.7 28.7 23.7 23.8 26.3 29.3
SHG 21.2 20.2 17.5 14.8 22.6 22.2 19.1 16.0 23.7 23.8 20.7 16.9
TC 20.4 21.5 24.2 27.0 21.8 22.3 25.0 27.9 23.0 23.0 25.5 28.6
kW 2.53 2.54 2.57 2.60 2.54 2.55 2.57 2.60 2.55 2.55 2.58 2.60
CMP 2.18 2.19 2.22 2.25 2.19 2.20 2.22 2.25 2.20 2.20 2.23 2.25
LDB 50.3 51.9 56.1 60.4 53.3 54.0 57.9 62.1 55.8 55.9 59.4 63.5
LWB 44.0 49.7 54.6 59.7 45.5 51.5 56.5 61.5 46.7 52.7 57.8 62.9
115
(46.1)
TCG 19.8 20.4 23.0 25.8 21.1 21.2 23.7 26.5 22.2 22.2 24.2 27.1
SHG 19.8 19.4 16.7 14.0 21.1 21.2 18.3 15.1 22.2 22.2 19.8 16.1
TC 19.1 19.7 22.2 25.0 20.4 20.4 23.0 25.8 21.4 21.5 23.5 26.4
kW 2.75 2.77 2.80 2.84 2.78 2.78 2.81 2.85 2.79 2.79 2.82 2.86
CMP 2.40 2.42 2.45 2.49 2.43 2.43 2.46 2.50 2.44 2.44 2.47 2.51
LDB 52.3 53.1 57.2 61.4 55.1 55.1 59.0 63.1 57.4 57.5 60.3 64.4
LWB 45.0 50.9 55.7 60.7 46.4 52.4 57.4 62.4 47.4 53.4 58.6 63.6
125
(51.7)
TCG 18.3 18.4 20.8 23.6 19.5 19.5 21.5 24.3 20.5 20.5 21.9 24.8
SHG 18.3 18.4 15.8 13.2 19.5 19.5 17.3 14.2 20.5 20.5 18.8 15.2
TC 17.6 17.6 20.1 22.9 18.8 18.8 20.7 23.5 19.7 19.8 21.2 24.0
kW 3.01 3.01 3.06 3.10 3.03 3.03 3.07 3.11 3.05 3.05 3.08 3.12
CMP 2.66 2.66 2.71 2.75 2.68 2.68 2.72 2.76 2.70 2.70 2.73 2.77
LDB 54.4 54.5 58.4 62.6 57.1 57.2 60.0 64.1 59.2 59.3 61.3 65.3
LWB 46.1 52.2 56.9 61.8 47.3 53.3 58.4 63.3 48.3 54.2 59.5 64.4
Rating Condition.
Not recommended for long--- term operation
BF --- B y p a s s Fa c t o r
CMP --- C o m p r e s so r
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
kW --- To t a l Po w e r
LDB --- L e a v i n g D r y Bu l b
LWB --- L e a v i n g We t B u l b
SHG --- Gross Sensible Capacity (1000 Btuh)
TC --- Total Net Cooling Capacity (1000 Btuh)
TCG --- Gross C ooling Ca pacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHG is based o n 80_F (26.7_C) edb temperature o f air entering indoor coil.
Below 80_F (26.7_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.7_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
40QAC/38HDR -- 40QAQ/38QR