a. 0E0: Communication Fault Between ODUs
1. Error display:
ODU display: 0E0
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error Definition
Communication error between header unit and follower unit (display on follower unit).
4. Possible causes:
• Incorrect address setting of ODU
• Communication lines between ODUs is not installed correctly
• Wiring between main board and communication adapter is not installed correctly
• Damaged main board or communication terminal block of ODU
Figure 35 - Communication Terminal Block of ODU
43