EasyManua.ls Logo

Carrier 38VMA096HDS5-1 - 0 C7 0 PL: High Module Temperature Protection

Carrier 38VMA096HDS5-1
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
y. 0C7 0PL: High Module Temperature Protection
5. Error display:
ODU display: 0PL/0C7
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error definition:
Error is reported when the temperature of the module is registered on the main board Tf > 172.4°F, and 0C7 is reported when
0PL occur 3 times within 100 minutes.
4. Possible causes:
Clogged fin of radiator resulting in poor heat transfer
Left/right fan connected in reverse order during maintenance
Damaged ambient temperature sensor for the module
Damaged main board
CN64: the control port of fan A
(left fan
)
CN65: the control port of fan B
(
right fan)
Fan module A:
corresponding
to the left fan
Fan module B: corresponding
to the right fan
66

Table of Contents