p. 0P1: Current Leakage Error
1. Error display:
ODU display: 0P1
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error definition:
Current leakage on ODU > 90–100mA and LED1 flashes on the leakage protection board.
4. Possible causes:
• Abnormal insulation resistance and leakage for unit parts
• Damaged leakage current transformer
• Damaged main board
55