z. L0~L9 10H4 / 20H4: Compressor INV Module Protection
Error Display:
For the L0~L9 error, the digital display on the main board is identical to that in standby status. Check to see each error
code. See the following table for more information.
If L0~L9 protection occur 3 times within a 60 minute period, 10H4 or 20H4 will be reported on the digital display of the
main board.
Compressor A Module Protection
Compressor B Module Protection
Red LED always lights
on
Green LED flashes
quickly
Red LED always lights
on
Green LED flashes
quickly
LED5
LED4
LED7
LED6
Applicable Models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)