E1: COMMUNICATION ERROR BETWEEN IDU AND ODU
1. Error display:
IDU display: E1
2. Applicable models:
All indoor units
3. Error definition:
• Communication error between IDU and ODU (Heat Pump or Single Phase VRF)
• Communication error between IDU and MDC (Heat Recovery)
4. Possible causes:
• Abnormal power supply for ODU (Heat Pump or Single Phase VRF) or MDC (Heat Recovery)
• Communication wire is loose, shorted, opened, or improperly connected
• Damaged main board of IDU
• Damaged main board of ODU (Heat Pump or Single Phase VRF) or MDC (Heat Recovery)
• Communication cable is too long
Check whether the communication wire is
shorted, open, loose or wired incorrectly
Is there a problem with
Is the total length of the communication
wire in the system over 3937 feet?
Replace the main board of heat pump ODU,
Ensure correct
power supply
Reconnect the line
Reduce the length
Replace the main board of IDU.
Turn on power.
Is the “E1” error cleared
YES
YES
YES
YES
NO
NO
NO
Error resolved
NO
the power supply for ODU (Heat Pump
and Single Phase VRF or MDC)?
Turn off power,
or replace MDC board for heat recovery system

Other manuals for Carrier 40VM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 40VM Series and is the answer not in the manual?

Carrier 40VM Series Specifications

General IconGeneral
BrandCarrier
Model40VM Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals