target speed. 
Power off
Power on
Replace the main board 
the system operates 
normally?
Error 
resolved
of IDU, and check whether
Is the blower wheel stuck?
Make sure the IDU power supply is correct
Check whether the wire from the fan motor to the 
indoor unit is loose
Check whether the communication wire is 
disconnected or loosened from main control board to 
the unit.
Check whether the
DC310V power between the red
 and black lines on the CN24 terminal of main 
 board of IDU is correct. Check whether the DC15V power  
 between the black and white lines on the CN24 terminal of main 
board of IDU is correct. 
Connect the special motor to CN24 terminal 
of main board. Power on and operate at low speed. 
Error 
Resolved
Remove obstacles
Reconnect to the previous motor 
and power on with E6 error remaining. Check 
whether the red indicator LED1 
lights up
Connect the wire
Connect the wire 
Power it on and restart IDU, is E6 error 
eliminated?
Replace the main 
board of IDU
Replace the main 
board of IDU
Apply proper 
Replace the main 
board of IDU
Replace the motor
YES
NO
YES
YES
NO
NO
NO
NO
NO
YES
NO
NO
YES
NO
NO
YES
YES
NO
Without a special motor
power supply 
Does the system operate normally?