32
NOTE: CFM values below recommended minimum may affect life of
motor.
Table 29 — 45R Size 4 ECM Calibration
SET
POINT
CFM
VCU
MANUAL %
DISPLAY
(OPTION 6)
ACU-0
REMOTE 0-10VDC
(0-20mA)
DC SIGNAL
(OPTION 7)
ACU-P
REMOTE
2-10VDC
(4-20mA)
DC SIGNAL
(OPTION 8)
VDC mA VDC mA
885 100 10.0 (20.0) 10.0 (20.0)
877 99 9.9 (19.8) 9.9 (19.8)
868 98 9.8 (19.6) 9.8 (19.7)
859 97 9.7 (19.4) 9.8 (19.5)
850 96 9.6 (19.2) 9.7 (19.4)
841 95 9.5 (19.0) 9.6 (19.2)
832 94 9.4 (18.8) 9.5 (19.0)
824 93 9.3 (18.6) 9.4 (18.9)
815 92 9.2 (18.4) 9.4 (18.7)
806 91 9.1 (18.2) 9.3 (18.6)
797 90 9.0 (18.0) 9.2 (18.4)
788 89 8.9 (17.8) 9.1 (18.2)
779 88 8.8 (17.6) 9.0 (18.1)
770 87 8.7 (17.4) 9.0 (17.9)
762 86 8.6 (17.2) 8.9 (17.8)
753 85 8.5 (17.0) 8.8 (17.6)
744 84 8.4 (16.8) 8.7 (17.4)
735 83 8.3 (16.6) 8.6 (17.3)
726 82 8.2 (16.4) 8.6 (17.1)
717 81 8.1 (16.2) 8.5 (17.0)
708 80 8.0 (16.0) 8.4 (16.8)
700 79 7.9 (15.8) 8.3 (16.6)
691 78 7.8 (15.6) 8.2 (16.5)
682 77 7.7 (15.4) 8.2 (16.3)
673 76 7.6 (15.2) 8.1 (16.2)
664 75 7.5 (15.0) 8.0 (16.0)
655 74 7.4 (14.8) 7.9 (15.8)
647 73 7.3 (14.6) 7.8 (15.7)
638 72 7.2 (14.2) 7.8 (15.5)
629 71 7.1 (14.0) 7.7 (15.4)
620 70 7.0 (13.8) 7.6 (15.2)
611 69 6.9 (13.6) 7.5 (15.0)
602 68 6.8 (13.6) 7.4 (14.9)
593 67 6.7 (13.4) 7.4 (14.7)
585 66 6.6 (13.2) 7.3 (14.6)
576 65 6.5 (13.0) 7.2 (14.4)
567 64 6.4 (12.8) 7.1 (14.2)
558 63 6.3 (12.6) 7.0 (14.1)
549 62 6.2 (12.4) 7.0 (13.9)
540 61 6.1 (12.2) 6.9 (13.8)
531 60 6.0 (12.0) 6.8 (13.6)
523 59 5.9 (11.8) 6.7 (13.4)
514 58 5.8 (11.6) 6.6 (13.3)
505 57 5.7 (11.4) 6.6 (13.1)
496 56 5.6 (11.2) 6.5 (13.0)
487 55 5.5 (11.0) 6.4 (12.8)
478 54 5.4 (10.8) 6.3 (12.6)
470 53 5.3 (10.6) 6.2 (12.5)
461 52 5.2 (10.4) 6.2 (12.3)
452 51 5.1 (10.2) 6.1 (12.2)
443 50 5.0 (10.0) 6.0 (12.0)
434 49 4.9 (9.8) 5.9 (11.8)
425 48 4.8 (9.6) 5.8 (11.7)
416 47 4.7 (9.4) 5.8 (11.5)
408 46 4.6 (9.2) 5.7 (11.4)
399 45 4.5 (9.0) 5.6 (11.2)
390 44 4.4 (8.8) 5.5 (11.0)
381 43 4.3 (8.6) 5.4 (10.9)
372 42 4.2 (8.4) 5.4 (10.7)
363 41 4.1 (8.2) 5.3 (10.6)
354 40 4.0 (8.0) 5.2 (10.4)
346 39 3.9 (7.8) 5.1 (10.2)
337 38 3.8 (7.6) 5.0 (10.1)
328 37 3.7 (7.4) 5.0 (9.9)
319 36 3.6 (7.2) 4.9 (9.8)
310 35 3.5 (7.0) 4.8 (9.6)
301 34 3.4 (6.8) 4.7 (9.4)
293 33 3.3 (6.6) 4.6 (9.3)
284 32 3.2 (6.4) 4.6 (9.1)
275 31 3.1 (6.2) 4.5 (9.0)
266 30 3.0 (6.0) 4.4 (8.8)
257 29 2.9 (5.8) 4.2 (8.6)
248 28 2.8 (5.6) 4.2 (8.5)
239 27 2.7 (5.4) 4.1 (8.3)
231 26 2.6 (5.2) 4.0 (8.2)
222 25 2.5 (5.0) 3.9 (8.0)
213 24 2.4 (4.8) 3.8 (7.8)
204 23 2.3 (4.6) 3.8 (7.7)
195 22 2.2 (4.4) 3.6 (7.5)
186 21 2.1 (4.2) 3.7 (7.4)
177 20 2.0 (4.0) 3.6 (7.2)
169 19 1.9 (3.8) 3.5 (7.0)
160 18 1.8 (3.6) 3.4 (6.9)
151 17 1.7 (3.4) 3.4 (6.7)
142 16 1.6 (3.2) 3.3 (6.6)
133 15 1.5 (3.0) 3.2 (6.4)
124 14 1.4 (2.8) 3.1 (6.2)
116 13 1.3 (2.6) 3.0 (6.1)
107 12 1.2 (2.4) 3.0 (5.9)
98 11 1.1 (2.2) 2.9 (5.8)
89 10 1.0 (2.0) 2.8 (5.6)
80 9 0.9 (1.8) 2.7 (5.4)
71 8 0.8 (1.6) 2.6 (5.3)
62 7 0.7 (1.4) 2.6 (5.1)
54 6 0.6 (1.2) 2.5 (5.0)
45 5 0.5 (1.0) 2.4 (4.8)
36 4 0.4 (0.8) 2.3 (4.6)
27 3 0.3 (0.6) 2.2 (4.5)
18 2 0.2 (0.4) 2.2 (4.3)
9 1 0.1 (0.2) 2.1 (4.2)
Table 29 — 45R Size 4 ECM Calibration (cont)
SET
POINT
CFM
VCU
MANUAL %
DISPLAY
(OPTION 6)
ACU-0
REMOTE 0-10VDC
(0-20mA)
DC SIGNAL
(OPTION 7)
ACU-P
REMOTE
2-10VDC
(4-20mA)
DC SIGNAL
(OPTION 8)
VDC mA VDC mA