9
11. Check all control connections (and/or electric) for proper 
installation.
12. Connect electrical power.
Balancing Carrier Fan Terminals 
 Carrier fan terminal units contain primary air dampers which, un-
der the control of a volume controller, regulate the amount of cold 
air distributed to the space.
45J,K,Q SERIES FLOW UNITS
The 45J,K,Q series flow terminals direct all primary air through 
the unit fan. The terminal is designed to operate with the fan sup
-
plying airflow equal to or greater than the airflow supplied by the 
VAV damper. To balance the unit, therefore, it is necessary to first 
set the fan flow, and then the VAV damper (primary) flow.
Each control option has specific procedures required for balancing 
the unit, but some steps are common to all 45J,K,Q units. The fan 
box adjustments described below must be made in conjunction 
with the adjustments described in the Speed Controller and Con
-
trol Adjustments section.
The VAV damper airflow may be set at the factory, but the fan air-
flow must be set in the field as described in “Setting of VAV (Pri-
mary) Airflow.”
Setting Fan Airflow
1. Set the controller to provide heating airflow demand only. 
Typically, this is accomplished by setting the thermostat to 
the highest possible temperature setting.
NOTE: A minimum of 0.1 in. wg downstream static pressure is 
required in the duct to ensure proper heater operation.
2. Determine that the VAV valve is fully closed and that the 
fan is rotating in the proper direction. (If the VAV damper 
is open when the fan is started and there is primary air in 
the system, the fan may start and run backward.)
3. Using a flow hood or duct traverse, determine the deliv-
ered fan airflow (cfm).
NOTE: Both flow hood and duct traverse are subject to measure-
ment errors. Be sure that all applicable measurement precautions 
are taken.
4. Compare the actual cfm in heating mode to the designed 
airflow. If there is a minimum setting for the VAV damper 
in heating mode (as recommended by ASHRAE [Ameri
-
can Society of Heating, Refrigeration, and Air Condition-
ing Engineers] Standard 62), this quantity is included in 
the total measured heating airflow to determine if the 
desired induction airflow level has been met.
5. Adjust the fan SCR at unit control box to achieve the 
desired airflow rate. Refer to Tables 
9-14 to ensure airflow 
through electric heaters meets the requirements before 
operating the heater.
Setting of VAV (Primary) Airflow
Adjustment of Set Points
Each 45J, 45K, and 45Q supplied with controls is equipped with a 
pneumatic or electronic volume controller which regulates the 
quantity of cold primary air entering the terminal and the condi
-
tioned space. If required airflow levels are specified with the job 
order, the minimum and maximum cfm levels will be set at the 
factory where applicable. If minimum and maximum levels are 
not specified, a default value of 0 is used for minimum setting at 
the factory. Other settings of minimum and maximum primary air
-
flow must be set in the field. Airflow (cfm) ranges for the primary 
air damper are shown in Tables 
9-14. The minimum primary air-
flow (other than zero) is the minimum flow rate controllable by 
the unit volume controller. The primary air damper can be set at 
zero for shutoff or at the minimum cfm listed.
Field Adjustment of Minimum and Maximum Airflow Set 
Points
Each 45J, 45K, and 45Q unit is equipped with a centerpoint aver-
aging airflow sensor which provides an amplified differential 
pressure that is proportional to the unit airflow. Output from this 
probe is used to provide a flow signal to both pneumatic and elec
-
tronic controls. Unit airflow (cfm) can be read directly from the 
flow probe on the unit (refer to Fig. 
9).
1. With the unit airflow from the fan set, turn on primary 
(VAV) air supply.
2. To set cfm in the field, connect a gage to the flow probe at 
the provided ‘T’ taps, and check the differential pressure. 
(Alternately, the total flow may be measured, and the pre
-
viously determined fan induction flow rate may be sub-
tracted from the total flow to determine VAV flow. 
However, for low primary settings, this may not be as 
accurate as the flow tap method.)
3. If a minimum VAV flow is required in heating mode, 
adjust the volume until the differential pressure corre
-
sponds to the cfm required.
4. Set the controller to provide maximum cooling demand. 
This is typically accomplished by first setting the thermo
-
stat to the lowest possible temperature setting.
 a. In most series fan boxes, the primary airflow rate is 
equal to the fan induction flow; in these cases, adjust the 
volume controller until a balance is achieved between 
fan induced airflow and primary airflow. When a bal
-
ance exists, a strip of paper hung at the induction port 
should hang straight down, and neither be blown in or 
out of the unit.
 b. If the primary airflow desired is less than the fan induc-
tion flow, adjust the volume controller until the differen-
tial pressure (measured through the flow probe as 
described above) corresponds to the cfm required. Verify 
that induction exists through the inlet ports, using the 
paper strips as described above. When induction exists, 
the paper strip should be pulled into the unit.
5. Return all reheat options to normal connections.
6. Cap the ‘T’ taps.
7. Reset the thermostat to a normal setting.
NOTE: It is normal for the total airflow to the room to increase 
slightly in full cooling mode.
NOTE: If the unit has electric heat or hot water heat, temporar-
ily disable these functions before balancing the fan.
If unit has optional electric heat disconnect downstream of fan 
motor connections to power, open disconnect.
If unit does not have optional electric heat disconnect, remove 
one electric heat power line connection. Be sure to insulate 
loose line from ground wire or other wires.