17 - CONNECTING THE UNIT TO A BMS SUPERVISION NETWORK
17.1. Enabling supervision
G. GENCONFIG
17.2. Confi guration of the supervision network
J. BMSCONF
U36a
Type of protocol
for supervision
network
Carel
RS485 serial card
KONNEX serial card (Confi guration by the Integrator)
BACNET MSTP RS485 card (Confi guration by the Integrator)
BACNET ETHERNET PCOWEB card (Confi guration by the Integrator)
ETHERNET PCOWEB card
LONWORKS FTT serial card
U36b
Unit address
for supervision
network : 001
Baud rate : 19200
Stop bit No : 2
Parity type : No
CU14
Supervision Y
Summer fcooling Y
Winter fheating N
Winter fcooling Y
Air refreshing Y
100% outdoor air N
17.3. Failure of BMS communication
U36c
Enable BMS communicat.
fault detection: Y
Time for fault: 15 m
Var.digital BMS fault
detection n. 174: Y
BMS commun. fault:Y
U40a
VALUES WITHOUT BMS
Temp. control
setpoint
Summer 26.0ßC
Winter 21.0ßC
U40b
VALUES WITHOUT BMS
Unit off/on
ON
U40d
VALUES WITHOUT BMS
DISCONNECTING
No. compressor stages
to disconnect: 0
No. el.heaters stages
to disconnect: 0
U40e
VALUES WITHOUT BMS
Start type
'ON-OFF schedule'
U40c
VALUES WITHOUT BMS
Winter/Summer select.
'autimatic' by ind.T.
SUMMER
U40f
VALUES WITHOUT BMS
Program select.
Daily start
M:1 T:1 W:1 T:1 F:1
S:1 Su: -Sun-(0=off)
U40f
VALUES WITHOUT BMS
SCHEDULE PROGR. N.1
Slot 1>06:30 to 11:00
Slot 2>11:30 to 13:30
Slot 3>15:00 to 19:00