EasyManua.ls Logo

Carrier 50HJ015 - Page 14

Carrier 50HJ015
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
8
Alternate
Drive
Components
Table,
50HJ024
UNIT
50HJ
MOTOR
HP
DRIVE
SOURCE
i
!
FAN
RPM
MOTOR
SHEAVE
DATUM
DIMENSION*
(in.)
MOTOR
SHEAVE
PART
NO.t
BLOWER
SHEAVE
DATUM
DIMENSION*
(in.)
BLOWER
SHEAVE
PART
NO.f
BELT
PART
NO.f
7V2
Field
1181
5.6
BK62
8.4
BK90
BX50
024
Th
Field
1244
5.9
BK65
8.4
BK90
BX51
V/2
Factory
1287
6
1
BK67
84
BK90
BX51
1V2
Field
1379
6.6
BK72
8.4
BK90
BX52
LEGEND
MPTA
Mechanical
Power
Transmission
Association
RMA
Rubber
Manufacturers’
Association
‘Datum
dimension
is
equal
to
the
old
pitch
diameter
per
RMA/MPTA
Standard
IP20-1977.
to
convert
to
new
pitch
diameter
per
RMA/
MPTA
Standard
IP20-1988,
add
0.3
in.
to
the
sheave
datum
dimension.
tPart
numbers
for
motor
sheave,
blower
sheave,
and
belt
are
Brown¬
ing
Catalog
part
numbers.
The
motor
sheaves
have
Browning
fixed
bore
sheaves
supplied
with
factory
drive
package.
Belt
Tension
Adjustment
To
adjust
belt
tension:
1.
Loosen
fan
motor
bolts.
2.
a.
015
units:
Move
motor
mounting
plate
up
or
down
for
proper
belt
tension
(
l
h
in.
deflection
with
one
finger),
b.
024
units:
Turn
motor
jacking
bolt
to
move
motor
mounting
plate
up
or
down
for
proper
belt
tension
(Vs
in.
deflection
at
midspan
with
one
finger
[9
lb
force]).
3.
Tighten
nuts.
4.
Adjust
bolts
and
nut
on
mounting
plate
to
secure
motor
in
fixed
position.
Condenser-Fan
Adjustment
(Fig.
22)
1.
Shut
off
unit
power
supply.
2.
Remove
fan
top-grille
assembly
and
loosen
fan
hub
screws.
3.
Adjust
fan
height
on
unit,
using
a
straightedge
placed
across
the
fan
orifice.
4.
Tighten
setscrews
and
replace
rubber
hubcap
to
prevent
hub
from
rusting
to
motor
shaft.
5.
Fill
hub
recess
with
permagum
if
rubber
hubcap
is
missing.
Economizer
Adjustment
Refer
to
Tables
9
and
10
for
economizer
checkout
procedures.
Make
certain
the
outdoor-air
damper
is
fully
closed
and
the
return-air
damper
is
fully
open
before
completing
the
following
steps.
1.
Turn
on
power
to
the
unit.
2.
Turn
the
thermostat
fan
switch
to
the
ON
position.
The
damper
will
go
to
the
vent
position.
3.
Adjust
the
vent
position
with
the
minimum
position
ad¬
justment
on
the
economizer
control
module.
See
Fig.
14.
Fig.
22
-
Condenser-Fan
Adjustment
4.
Set
the
system
selector
switch
to
COOL
position
and
set
the
cooling
temperature
selector
to
its
lowest
setting.
NOTE:
The
cooling
mode
may
also
be
simulated
by
remov¬
ing
the
thermostat
wires
from
terminals
Y1
and
Y2
and
in¬
stalling
a
jumper
between
terminals
R
and
Y1,
Refer
to
unit
label
diagram
for
terminal
locations.
5.
Set
the
outdoor-air
thermostat
(OAT)
located
in
the
econo¬
mizer
section
of
the
unit
to
75
F.
6.
If
the
outdoor
temperature
is
below
75
F,
the
econo¬
mizer
will
control
the
mixed
air
with
the
mixed-air
sen¬
sor.
If
the
outdoor
air
is
above
75
F,
place
a
jumper
around
the
contacts
of
the
OAT
7.
Jumper
terminal
T
to
terminal
T1
on
the
module
(see
Fig.
14).
The
economizer
will
go
to
the
full
open
position.
The
outdoor-air
damper
will
go
to
the
full
open
position,
and
the
return-air
damper
will
go
to
the
full
closed
position.
8.
Adjust
mechanical
linkage,
if
necessary,
for
correct
po¬
sitioning.
It
may
be
necessary
to
remove
the
filters
to
adjust
the
linkage.
9.
Remove
the
jumper
from
around
the
contacts
of
the
OAT
if
installed
in
Step
6.
Remove
the
jumper
from
terminals
T
and
T1
installed
in
Step
7.
10.
I
f
the
cooling
mode
was
simulated
to
operate
the
unit
in
Step
4,
remove
the
jumper
and
reconnect
the
ther¬
mostat
wires
to
terminals
Y1
and
Y2.
Power
Failure
Dampers
have
a
spring
return
In
event
of
power
failure,
dampers
will
return
to
fully
closed
posi¬
tion
until
power
is
restored.
Do
not
manually
operate
damper
motor.
Refrigerant
Charge
Amount
of
refrigerant
charge
is
listed
on
unit
nameplate
and
in
Table
1.
Refer
to
Carrier
GTAC
II;
Module
5;
Charging,
Recovery,
Recycling,
and
Reclamation
section
for
charging
methods
and
procedures.
Unit
panels
must
be
in
place
when
unit
is
operating
dur¬
ing
charging
procedure.
NO
CHARGE
Use
standard
evacuating
techniques.
After
evacuating
system,
weigh
in
the
specified
amount
of
refrigerant
(refer
to
Table
1).
LOW
CHARGE
COOLING
-
Using
appropriate
cooling
charging
chart
(see
Fig.
23
and
24),
add
refrigerant
until
conditions
of
the
chart
are
met.
Note
that
charging
charts
are
different
from
those
normally
used.
Charts
are
based
on
charging
units
to
correct
superheat
for
various
operating
con¬
ditions.
An
accurate
pressure
gage
and
temperature
sensing
device
are
required.
Connect
temperature
sensing
device
to
service
port
on
suction
line
and
insulate
it
so
that
outdoor
ambient
temperature
does
not
affect
reading.
Indoor-air
cfm
must
be
within
normal
operating
range
of
unit.
14

Related product manuals