Carrier 50HJ015 - Page 15

Carrier 50HJ015
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
9
-
Economizer
Checkout
Procedures
100
test
procedure
RESULTS
A
Disconnect
power
at
TR
and
TR1
Disconnect
jumper
between
P
and
PI.
See
Fig
14
B.
Jumper
TR
to
1
C.
Jumper
T1
to
T.
D.
Disconnect
outdoor-air
thermostat
connections
from
S
Q
and
+
Factory-installed
800
ohm
resistor
should
remain
connected
to
S
R
and
+.
E
Reconnect
power
to
terminals
TR
and
TR1
1.
LED
(light-emitting
diode)
should
be
off.
2.
Motor
is
in
closed
position
TEST
PROCEDURE
RESULTS
A
Disconnect
factory-installed
resistor
from
terminals
S
R
and
+
1
LED
(light-emitting
diode)
should
be
on
2.
Motor
drives
toward
open
Table
10
High
and
Low
Outdoor-Air
Temperature
Simulation
TEST
PROCEDURE
RESULTS
A
Reconnect
factory-
installed
800
ohm
resistor
between
terminals
S
R
and
+
B.
Connect
1200
ohm
checkout
resistor
between
terminals
S
Q
and
+.
C.
Turn
set
point
potentiom¬
eter
to
position
A
Low
outdoor-air
temperature
test
results:
1
LED
(light-emitting
diode)
should
be
on
2
Motor
drives
toward
open
D.
Turn
set
point
potentiom¬
eter
to
position
D
E
Disconnect
1200
ohm
checkout
resistor
High
outdoor-air
temperature
test
results
1
LED
should
be
off
2
Motor
drives
toward
closed.
TO
USE
COOLING
CHARGING
CHART
-
Take
out¬
door
ambient
temperature
and
read
the
suction
pressure
gage.
Refer
to
appropriate
chart
to
determine
correct
suction
tem¬
perature.
If
suction
temperature
is
high,
add
refrigerant.
If
suction
temperature
is
low,
carefully
reclaim
some
of
the
charge.
Recheck
suction
pressure
as
charge
is
adjusted
Filter
Drier
Replace
whenever
refrigerant
system
is
exposed
to
atmosphere.
40
50
60
SUCTION
LINE
TEMP
(F)
Fig.
23
Cooling
Charging
Chart
50HJ015
Fig.
24
-
Cooling
Charging
Chart
-
50HJ024
i
15