EasyManua.ls Logo

Carrier 58ED - Burner Orifices; Step 7 - Make Electrical Connections

Carrier 58ED
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58ED,PB
Horizontal
Gas-Fired
Furnaces
HEATING
&
COOLING
Support
all
gas
piping
independent
of
the
fui
nace.
For
propane
gas,
a
tank
regulator
is
required
to
reduce
supply
pressure
to
12-13
in.
wg.
For
manifold
pressure,
see
Table
6.
Check
all
piping
for
leaks
using
soapy
water
and
a
brush.
A
CAUTION
Never
use
an
open
flame
when
testing
for
gas
leaks!
Use
a
soap
and
water
solution
A
1/8
in.
NPT
plugged
tap
accessible
for
test
gage
connection
must
be
installed
immediately
upstream
of
the
gas
supply
connection
to
the
furnace
if
one
is
not
supplied
on
gas
valve.
BURNER
ORIFICES
The
furnace
is
supplied
with
standard
orifices
for
the
gas
shown
on
the
rating
plate.
Table
6
shows
combinations
of
heating
values
and
specific
gravities
for
various
fuels,
from
which
proper
input
may
be
obtained
Regardless
of
the
type
of
gas
used,
when
installation
is
at
an
elevation
of
2000
ft
or
more
above
sea
level,
orifices
may
need
to
be
changed,
depending
on
local
gas
value.
For
operation
at
elevations
above
2000
ft,
input
ratings
should
be
reduced
at
the
rates
of
4%
for
each
1000
ft
above
sea
level.
To
change
orifices,
remove
the
burner
removal
cover
on
the
gas
valve
side
of
unit.
Remove
manifold
locking
device
and
slide
the
manifold
tray
back
until
each
burner
is
clear
of
heat
exchanger
tube.
See
Fig.
5
Pull
the
manifold
tray
forward
until
burners
are
clear
of
furnace.
Remove
the
locking
device
from
each
burner
and
pull
each
burner
back
off
the
orifice.
A
CAUTION
Take
care
when
removing
the
pilot
burner
not
to
damage
the
pilot
gas
line.
After
removing
orifices,
ensure
the
new
orifices
are
seated
properly
and
tightened.
Replace
burners
correctly
and
secure
with
the
locking
device
before
replacing
and
securing
the
manifold
assembly.
A
CAUTION
The
manifold
must
be
properly
positioned
in
order
to
engage
the
locking
mechanism
Table
6
Burner
Orifices
TYPE
OF
GAS
(Heating
Value
SP
GR)
BTU
PER
CU
FT
ORIFICE
SIZE
(Drill
No.)
NATURAL
MANIFOLD
PRESS.
3.5
in.
wg
800
0.6
43
900
0.6
44
1000
-
0.6
45
1100
-
0.6
46
PROPANE
MANIFOLD
PRESS.
10
in.
wg
2500
1.53
54
Fig.
5
Burners
Removed
From
Furnace
After
securing
the
manifold
assembly,
replace
all
other
components
and/or
wiring,
being
sure
that
all
connec¬
tions
and
screws
are
tightened.
A
WARNING
If
it
is
necessary
to
adjust
the
manifold
pressure
more
than
0.3
in.
wg,
the
orifices
must
be
changed
A
WARNING
Never
set
the
furnace
input
rate
above
that
shown
on
rating
plate.
Use
the
following
formula
to
determine
the
furnace
input
rate:
Input
(Btuh)
=
Heating
Value
of
Gas
(Btu/cu
ft)
_
x
7200
sec/2
hr
_
Time
in
sec
for
2
cu
ft
of
gas
Example.
If
the
heating
value
of
natural
gas
is
1015
Btu/cu
ft
and
it
takes
75
seconds
to
burn
2cuft
of
gas,
then:
Input
(Btuh)
=
1015
Btu/cu
ft
x
7200
sec/2
hr
75
sec/2
cu
ft
Input
=
97,440
Btuh
When
checking
rate,
make
sure
all
other
gas
appliances
are
shut
off
except
for
pilot
burners.
Step
7
Make
Electrical
Connections
The
control
system
depends
on
the
correct
polarity
of
the
power
supply.
Connect
field
power
wiring
and
field
ground
wire
as
shown
in
Fig.
6
and
7.
A
WARNING
The
unit
cabinet
must
have
a
separate
uninterrupted
or
unbroken
electrical
ground
to
minimize
personal
injury
if
an
electrical
fault
should
occur.
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.
Bookll
14
PC101
Catalog
No
535-834
PrintedinUSA
Form
58ED,PB-1SI
Pg6
6-85
Replaces:
58PB-1SI
Tab
16a
18a
For
replacement
items
use
Carrier
Specified
Parts

Related product manuals