EasyManua.ls Logo

Carrier 58GFA - Air Intake and Filter Setup; Outside Air Intake Requirements; Filter Arrangement and Installation

Carrier 58GFA
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If the furnace is installed on a raised platform to provide a return-
air plenum, and return air is taken directly from the hallway or
space adjacent to the furnace, all air for combustion must come
from outdoors.
2. All air from outside the structure:
a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space. (See Fig. 3.)
For Example:
58GFA FURNACE
INPUT BTUH
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
63,000 16.0 5
84,000 21.0 6
105,000 26.5 6
126,000 31.5 7
147,000 37.0 7
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of the total input
for all equipment within the confined space.
For Example:
58GFA FURNACE
INPUT BTUH
FREE AREA PER
OPENING (SQ IN.)
ROUND PIPE
(IN. DIA)
63,000 31.5 7
84,000 42.0 8
105,000 52.5 9
126,000 63.0 9
147,000 73.5 10
When ducts are used, they must be of the same cross-sectional area
as the free area of the openings to which they connect. The
minimum dimension of rectangular ducts must not be less than 3
in. (See Fig. 3.)
Do not install the furnace on its back; safety control operation
will be adversely affected. Never connect return-air ducts to
the back of the furnace. Failure to follow this warning can
cause a fire, personal injury, or death.
Step 3—Filter Arrangement
The factory-supplied filter(s) is shipped in the blower compart-
ment. Determine location for the filter and move filter retaining
hardware, if necessary, before attaching the return-air duct. After
the return-air duct has been connected to the furnace, install the
filter(s) inside the furnace blower compartment. See Fig. 4 for side
return application and Fig. 5 for bottom return application.
Fig. 2—Air for Combustion and Ventilation
(Inside Air)
A89012
SUPPLY
AIR
6 MIN
(FRONT)
RETURN AIR
VENT THROUGH ROOF
1 SQ IN.
PER 1000
BTUH
*
IN DOOR
OR WALL
12 MAX
1 SQ IN.
PER 1000
BTUH
*
IN DOOR
OR WALL
12 MAX
INTERIOR
HEATED
SPACE
* Minimum opening size is 100 square in. with
minimum dimensions of 3-In.
Minimum of 3-In. when type-B1 vent is used.
UNCONFINED
SPACE
CONFINED
SPACE
Fig. 3—Air for Combustion and Ventilation
(Outside Air)
A89013
1 SQ IN.
PER
4000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
SUPPLY
AIR
VENT
THROUGH
ROOF
D
B
A
C
E
1 SQ IN.
PER 4000
BTUH*
DUCT
TO
OUTDOORS
RETURN AIR
1 SQ IN.
PER 2000
BTUH*
1 SQ IN.
PER 2000
BTUH*
DUCTS
TO
OUTDOORS
12 MAX
12
MAX
12 MAX
Use any of the following
combinations of openings:
A & B C & D D & E F & G
NOTE:
*Minimum dimensions of 3-In.
CONFINED
SPACE
12
MAX
12
MAX
OUTDOORS
1 SQ IN.
PER
4000
BTUH*
F
G
4

Other manuals for Carrier 58GFA

Related product manuals