The opening shall commence within 12 in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least 1
in. (25 mm) from the sides and back and 6 in. (150 mm) from the
front. The opening shall directly communicate with the outdoors
or shall communicate through a vertical or horizontal duct to the
outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
Indoor Combustion AirE NFPA & AGA
Standard and Known--Air--Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution,
if the Standard or Known--Air--Infiltration Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
Many homes require air to be supplied from outdoors
for furnace combustion, ventilation, and dilution of flue
gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
!
WARNING
Table 1 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors
FURNACE
INPUT
(BTUH)
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/K W)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
44,000 22 ( 14194) 6 ( 152) 14.7 ( 9484) 5 ( 127) 11 ( 7096) 4 ( 102)
66,000 33 ( 21290) 7 ( 178) 22 ( 14193) 6 ( 152) 16.5 ( 10645) 5 (127)
88,000 44 ( 28387) 8 ( 203) 29.3 ( 18903) 7 ( 178) 22 ( 14193) 6 (152)
110,000 55 ( 35484) 9 ( 229) 36.7 ( 23677) 7 ( 178) 27.5 ( 17742) 6 (152)
132,000 66 ( 42580) 10 (254) 44 ( 28387) 8 ( 203) 33 ( 21290) 7 (178)
154,000 77 ( 49677) 10 (254) 51.3 ( 33096) 9 ( 229) 38.5 ( 24839) 8 (203)
Note: Not all models have these sizes.
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening
88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
Table 2 – Minimum Space Volumes for 100% Combustion, Ventilation, a nd Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30 40 50 44 66 88 110 132 154
Space Volume Ft
3
(M
3
)
0.60
1,050
(29.7)
1,400
(39.6)
1,750
(49.5)
1,100
(31.1)
1,650
(46.7)
2,200
(62.2)
2,750
(77.8)
3,300
(93.4)
3,850
(109.0)
0.50
1,260
(35.6)
1,680
(47.5)
2,100
(59.4)
1,320
(37.3)
1,980
(56.0)
2,640
(74.7)
3,300
(93.4)
3,960
(112.1)
4,620
(130.8)
0.40
1,575
(44.5)
2,100
(59.4)
2,625
(74.3)
1,650
(46.7)
2,475
(70.0)
3,300
(93.4)
4,125
(116.8)
4,950
(140.1)
5,775
(163.5)
0.30
2,100
(59.4)
2,800
(79.2)
3,500
(99.1)
2,200
(62.2)
3,300
(93.4)
4,400
(124.5)
5,500
(155.7)
6,600
(186.8)
7,700
(218.0)
0.20
3,150
(89.1)
4,200
(118.9)
5,250 (148.6)
3,300
(93.4)
4,950
(140.1)
6,600
(186.8)
8,250
(233.6)
9,900
(280.3)
11,550
(327.0)
0.10
6,300
(178.3)
8,400
(237.8)
10,500
(297.3)
6,600
(186.8)
9,900
(280.3)
13,200
(373.7)
16,500
(467.2)
19,800
(560.6)
23,100
(654.1)
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
Note: Not all models have these sizes.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300
mm) of the ceiling and the second opening MUST
commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 1.
c. TWO HORIZONTAL DUCTS require 1 sq. in. (645
sq. mm) of free area per 2,000 Btuh (1,100 mm
2
/kW)
of combined input for all gas appliances in the space
per Fig. 7 and Table 1.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq. in. (645 sq. mm) of free area per 4,000 Btuh (550
mm
2
/kW) for combined input of all gas appliances in
the space per Fig. 7 and Table 1.
3. ONE OUTDOOR OPENING requires:
a. 1 sq. in. (645 sq. mm) of free area per 3,000 Btuh
(734 mm
2
/kW) for combined input of all gas appli-
ances in the space per Table 1 and
b. Not less than the sum of the areas of all vent connect-
ors in the space.