Table 69 — VFD Parameters, Standard + Tier, for 380 V/60 Hz Units, 30XV225-275
PARAMETER
SETTING
DESCRIPTION
30XV225 30XV250 30XV275
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-03 torque profile
Compressor
Torque
0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-20 motor kW
size
dependent
160 97 13.8 9.2 160 160 13.8 13.8 160 160 13.8 13.8
1-22 motor volts
motor
dependent
380 380 380 380 380 380 380 380 380 380 380 380
1-23
motor
frequency
motor
dependent
98 105 60 60 98 98 60 60 98 98 60 60
1-24
motor
amperage
size
dependent
338 217 42.6 28.4 327 327 42.6 42.6 340 340 42.6 42.6
1-25 motor rpm
size
dependent
5830 6240 1130 1130 5830 5830 1130 1130 5830 5830 1130 1130
1-71
compressor
start delay
0s 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-73 Flying Restart NO N/AN/A0—0—N/AN/A0—0—N/AN/A0—0—
1-78
starting
frequency
26hz 26 26 N/A N/A 26 26 N/A N/A 26 26 N/A N/A
1-79
Comp start
maxtime to
trip
5s 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A
1-80
function at
stop
coast 000000000000
1-90
motor ther-
mal protection
0 000000000000
3-02 min ref 0 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
3-03 max reference
size
dependent
83 93 60 60 80 80 60 60 85 85 60 60
3-13 type reference remote 110011001100
3-15 src ref#1 no function 000000000000
3-16 src ref#2 no function 000000000000
3-41 ramp up 100s 100 100 20 20 100 100 20 20 100 100 20 20
3-42 ramp down 100s 100 100 20 20 100 100 20 20 100 100 20 20
3-82
starting ramp
time
3s 3 3 N/A N/A 3 3 N/A N/A 3 3 N/A N/A
4-10
motor speed
direct
clockwise 000000000000
4-12
motor speed
low limit
26Hz 26265—5—26265—5—26265—5—
4-14
motor speed
high limit
95Hz 83 93 60 60 80 80 60 60 85 85 60 60
4-16 torque limit
size
dependent
150 150 150 150 150 150 150 150 150 150 150 150
4-18 current limit
size
dependent
110 110 110 110 110 110 110 110 110 110 110 110
4-19
max output
frequency
size
dependent
84 94 N/A N/A 81 81 N/A N/A 86 86 N/A N/A
5-12 DI #27 Coast Inverse 220022002200
5-19
DI#37 safe
stop
safe stop
alarm
1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
5-40[36] relay 1
control word
bit 11
36 36 N/A N/A 36 36 N/A N/A 36 36 N/A N/A
5-40[5] relay 2 running 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A
8-01 control site
digital & con-
trol word
000000000000
8-02
control
source
FC
port=RS485
111111111111
8-03 time out time 10s 10 10 10 10 10 10 10 10 10 10 10 10
8-04
time out func-
tion
stop and trip 552255225522
14-00 Pattern [AVM] 60AVM N/AN/A0—0—N/AN/A0—0—N/AN/A0—0—
14-01
switching
frequency
3kHz 446644664466
14-03
over-
modulation
yes 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-10 main failure alarm 6 6 N/A N/A 6 6 N/A N/A 6 6 N/A N/A
14-11
Mains voltage
at Mains fault
345V 300 300 N/A N/A 300 300 N/A N/A 300 300 N/A N/A
14-50 RFI Filter on 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-60
function at
overtemp
derate 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-61
inverter
overload
derate 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A