Table 70 — VFD Parameters, Standard + Tier, for 380 V/60 Hz Units, 30XV300-350
PARAMETER
SETTING
DESCRIPTION
30XV300 30XV325 30XV350
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 0 0 N/A — N/A — 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A —
1-03 torque profile
Compressor
Torque
0 0 N/A — N/A — 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A —
1-20 motor kW
size
dependent
160 160 16.1 — 16.1 — 160 160 9.2 9.2 9.2 9.2 242 160 11.5 9.2 16.1 —
1-22 motor volts
motor
dependent
380 380 380 — 380 — 380 380 380 380 380 380 380 380 380 380 380 —
1-23
motor
frequency
motor
dependent
98 98 60 — 60 — 98 98 60 60 60 60 95 98 60 60 60 —
1-24
motor
amperage
size
dependent
358 358 49.7 — 49.7 — 394 394 28.4 28.4 28.4 28.4 534 387 35.5 28.4 49.7 —
1-25 motor rpm
size
dependent
5830 5830 1130 — 1130 — 5830 5830 1130 1130 1130 1130 5650 5830 1130 1130 1130 —
1-71
compressor
start delay
0s 0 0 N/A — N/A — 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A —
1-73 Flying Restart NO N/AN/A0—0—N/AN/A0000N/AN/A000—
1-78
starting
frequency
26hz 26 26 N/A — N/A — 26 26 N/A N/A N/A N/A 26 26 N/A N/A N/A —
1-79
Comp start
maxtime to
trip
5s 5 5 N/A — N/A — 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A —
1-80
function at
stop
coast 000—0—00000000000—
1-90
motor ther-
mal protection
0 000—0—00000000000—
3-02 min ref 0 0 0 N/A — N/A — 0 0 N/A N/A N/A N/A 0 0 N/A N/A N/A —
3-03 max reference
size
dependent
90 90 60 — 60 — 98 98 60 60 60 60 75 90 60 60 60 —
3-13 type reference remote 110—0—11000011000—
3-15 src ref#1 no function 000—0—00000000000—
3-16 src ref#2 no function 000—0—00000000000—
3-41 ramp up 100s 100 100 20 — 20 — 100 100 20 20 20 20 100 100 20 20 20 —
3-42 ramp down 100s 100 100 20 — 20 — 100 100 20 20 20 20 100 100 20 20 20 —
3-82
starting ramp
time
3s 3 3 N/A — N/A — 3 3 N/A N/A N/A N/A 3 3 N/A N/A N/A —
4-10
motor speed
direct
clockwise 000—0—00000000000—
4-12
motor speed
low limit
26Hz 26265—5—262655552626555—
4-14
motor speed
high limit
95Hz 90 90 60 — 60 — 98 98 60 60 60 60 75 90 60 60 60 —
4-16 torque limit
size
dependent
150 150 150 — 150 — 150 150 150 150 150 150 150 150 150 150 150 —
4-18 current limit
size
dependent
110 110 110 — 110 — 110 110 110 110 110 110 110 110 110 110 110 —
4-19
max output
frequency
size
dependent
91 91 N/A — N/A — 99 99 N/A N/A N/A N/A 76 91 N/A N/A N/A —
5-12 DI #27 Coast Inverse 220—0—22000022000—
5-19
DI#37 safe
stop
safe stop
alarm
1 1 N/A — N/A — 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A —
5-40[36] relay 1
control word
bit 11
36 36 N/A — N/A — 36 36 N/A N/A N/A N/A 36 36 N/A N/A N/A —
5-40[5] relay 2 running 5 5 N/A — N/A — 5 5 N/A N/A N/A N/A 5 5 N/A N/A N/A —
8-01 control site
digital & con-
trol word
000—0—00000000000—
8-02
control
source
FC
port=RS485
111—1—11111111111—
8-03 time out time 10s 10 10 10 — 10 — 10 10 10 10 10 10 10 10 10 10 10 —
8-04
time out func-
tion
stop and trip 552—2—55222255222—
14-00 Pattern [AVM] 60AVM N/AN/A0—0—N/AN/A0000N/AN/A000—
14-01
switching
frequency
3kHz 446—6—44666644666—
14-03
over-
modulation
yes 1 1 N/A — N/A — 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A —
14-10 main failure alarm 6 6 N/A — N/A — 6 6 N/A N/A N/A N/A 6 6 N/A N/A N/A —
14-11
Mains voltage
at Mains fault
345V 300 300 N/A — N/A — 300 300 N/A N/A N/A N/A 300 300 N/A N/A N/A —
14-50 RFI Filter on 1 1 N/A — N/A — 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A —
14-60
function at
overtemp
derate 1 1 N/A — N/A — 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A —
14-61
inverter
overload
derate 1 1 N/A — N/A — 1 1 N/A N/A N/A N/A 1 1 N/A N/A N/A —