169
Table 129 — VFD Parameters, Mid Tier, for 440 V/50 Hz Units, 30XV140-200
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV140 30XV160 30XV180 30XV200
COMP FAN COMP FAN COMP FAN COMP FAN
NUMBER DESCRIPTION A B A1 A2 B1 B2 A B A1 A2 B1 B2 A B A1 A2 B1 B2 A B A1 A2 B1 B2
0-40
hand on
button
disabled 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-03 torque profile
Compressor
Torque
0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-20 motor kW
size
dependent
97 97 9.2 9.2 97 97 11.5 11.5 97 97 11.5 11.5 97 97 13.8 13.8
1-22 motor volts
motor
dependent
380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380
1-23
motor
frequency
motor
dependent
105 105 60 60 105 105 60 60 105 105 60 60 105 105 60 60
1-24
motor
amperage
size
dependent
175 175 28.4 28.4 188 188 35.5 35.5 219 219 35.5 35.5 241 241 42.6 42.6
1-25 motor rpm
size
dependent
6240 6240 1130 1130 6240 6240 1130 1130 6240 6240 1130 1130 6240 6240 1130 1130
1-71
compressor
start delay
0s 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
1-73 Flying Restart NO N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0
1-78
starting
frequency
26hz 26 26 N/A N/A 26 26 N/A N/A 26 26 N/A N/A 26 26 N/A N/A
1-79
Comp start
maxtime to trip
5s 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A
1-80
function at
stop
coast 0000000000000000
1-90
motor thermal
protection
0 0000000000000000
3-02 min ref 0 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A
3-03 max reference
size
dependent
75 75 60 60 85 85 60 60 95 95 60 60 105 105 60 60
3-13 type reference remote 1100110011001100
3-15 src ref#1 no function 0000000000000000
3-16 src ref#2 no function 0000000000000000
3-41 ramp up 100s 100 100 20 20 100 100 20 20 100 100 20 20 100 100 20 20
3-42 ramp down 100s 100 100 20 20 100 100 20 20 100 100 20 20 100 100 20 20
3-82
starting ramp
time
3s 3 3 N/A N/A 3 3 N/A N/A 3 3 N/A N/A 3 3 N/A N/A
4-10
motor speed
direct
clockwise 0000000000000000
4-12
motor speed
low limit
26Hz 26 26 5 5 26 26 5 5 26 26 5 5 26 26 5 5
4-14
motor speed
high limit
95Hz
75 75 60 60 85 85 60 60 95 95 60 60 105 105 60 60
4-16 torque limit
size
dependent
150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
4-18 current limit
size
dependent
110 110 110 110 110 110 110 110 110 110 110 110 110 110 110 110
4-19
max output
frequency
size
dependent
76 76 N/A N/A 86 86 N/A N/A 96 96 N/A N/A 106 106 N/A N/A
5-12 DI #27 Coast Inverse 2200220022002200
5-19
DI#37 safe
stop
safe stop
alarm
1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
5-40[36] relay 1
control word
bit 11
36 36 N/A N/A 36 36 N/A N/A 36 36 N/A N/A 36 36 N/A N/A
5-40[5] relay 2 running 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A 5 5 N/A N/A
8-01 control site
digital & con-
trol word
0000000000000000
8-02 control source
FC
port=RS485
1111111111111111
8-03 time out time 10s 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
8-04
time out func-
tion
stop and trip 5522552255225522
14-00 Pattern [AVM] 60AVM N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0 N/A N/A 0 0
14-01
switching
frequency
3kHz 4466446644664466
14-03
over-
modulation
yes 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-10 main failure alarm 6 6 N/A N/A 6 6 N/A N/A 6 6 N/A N/A 6 6 N/A N/A
14-11
Mains voltage
at Mains fault
345V 352 352 N/A N/A 352 352 N/A N/A 352 352 N/A N/A 352 352 N/A N/A
14-50 RFI Filter on 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-60
function at
overtemp
derate 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A
14-61
inverter
overload
derate 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A 1 1 N/A N/A