170
Table 130 — VFD Parameters, Mid Tier, for 440 V/50 Hz Units, 30XV225-275
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV225 30XV250 30XV275
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 00N/A
N/A
00N/A
N/A
00N/A
N/A
1-03 torque profile
Compressor
Torque
00N/A
N/A
00N/A
N/A
00N/A
N/A
1-20 motor kW
size
dependent
160 97 16.1
11.5
160 160 16.1
16.1
160 160 16.1
16.1
1-22 motor volts
motor
dependent
380 380 380
380
380 380 380
380
380 380 380
380
1-23
motor
frequency
motor
dependent
98 105 60
60
98 98 60
60
98 98 60
60
1-24
motor
amperage
size
dependent
327 209 49.7
35.5
310 310 49.7
49.7
336 336 49.7
49.7
1-25 motor rpm
size
dependent
5830 6240 1130
1130
5830 5830 1130
1130
5830 5830 1130
1130
1-71
compressor
start delay
0s 00N/A
N/A
00N/A
N/A
00N/A
N/A
1-73 Flying Restart NO N/A N/A 0
0
N/A N/A 0
0
N/A N/A 0
0
1-78
starting
frequency
26hz 26 26 N/A
N/A
26 26 N/A
N/A
26 26 N/A
N/A
1-79
Comp start
maxtime to
trip
5s 55N/A
N/A
55N/A
N/A
55N/A
N/A
1-80
function at
stop
coast 000
0
000
0
000
0
1-90
motor ther-
mal protection
0 000
0
000
0
000
0
3-02 min ref 0 00N/A
N/A
00N/A
N/A
00N/A
N/A
3-03 max reference
size
dependent
83 93 60
60
80 80 60
60
85 85 60
60
3-13 type reference remote 110
0
110
0
110
0
3-15 src ref#1 no function 000
0
000
0
000
0
3-16 src ref#2 no function 000
0
000
0
000
0
3-41 ramp up 100s 100 100 20
20
100 100 20
20
100 100 20
20
3-42 ramp down 100s 100 100 20
20
100 100 20
20
100 100 20
20
3-82
starting ramp
time
3s 33N/A
N/A
33N/A
N/A
33N/A
N/A
4-10
motor speed
direct
clockwise 000
0
000
0
000
0
4-12
motor speed
low limit
26Hz 26 26 5
5
26 26 5
5
26 26 5
5
4-14
motor speed
high limit
95Hz 83 93 60
60
80 80 60
60
85 85 60
60
4-16 torque limit
size
dependent
150 150 150
150
150 150 150
150
150 150 150
150
4-18 current limit
size
dependent
110 110 110
110
110 110 110
110
110 110 110
110
4-19
max output
frequency
size
dependent
84 94 N/A
N/A
81 81 N/A
N/A
86 86 N/A
N/A
5-12 DI #27 Coast Inverse 220
0
220
0
220
0
5-19
DI#37 safe
stop
safe stop
alarm
11N/A
N/A
11N/A
N/A
11N/A
N/A
5-40[36] relay 1
control word
bit 11
36 36 N/A
N/A
36 36 N/A
N/A
36 36 N/A
N/A
5-40[5] relay 2 running 55N/A
N/A
55N/A
N/A
55N/A
N/A
8-01 control site
digital & con-
trol word
000
0
000
0
000
0
8-02
control
source
FC
port=RS485
111
1
111
1
111
1
8-03 time out time 10s 10 10 10
10
10 10 10
10
10 10 10
10
8-04
time out func-
tion
stop and trip 552
2
552
2
552
2
14-00 Pattern [AVM] 60AVM N/A N/A 0
0
N/A N/A 0
0
N/A N/A 0
0
14-01
switching
frequency
3kHz 446
6
446
6
446
6
14-03
over-
modulation
yes 11N/A
N/A
11N/A
N/A
11N/A
N/A
14-10 main failure alarm 66N/A
N/A
66N/A
N/A
66N/A
N/A
14-11
Mains voltage
at Mains fault
345V 352 352 N/A
N/A
352 352 N/A
N/A
352 352 N/A
N/A
14-50 RFI Filter on 11N/A
N/A
11N/A
N/A
11N/A
N/A
14-60
function at
overtemp
derate 11N/A
N/A
11N/A
N/A
11N/A
N/A
14-61
inverter
overload
derate 11N/A
N/A
11N/A
N/A
11N/A
N/A