Table 162 — VFD Parameters, High Tier, for 440 V/50 Hz Units, 30XV140-180
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV140 30XV160 30XV180
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 00N/A
—
N/A
—
00N/A
—
N/A
—
00N/A
—
N/A
—
1-03 torque profile
Compressor
Torque
00N/A
—
N/A
—
00N/A
—
N/A
—
00N/A
—
N/A
—
1-20 motor kW
size
dependent
97 97 11.5
—
11.5
—
97 97 13.8
—
13.8
—
97 97 13.8
—
13.8
—
1-22 motor volts
motor
dependent
380 380 380
—
380
—
380 380 380
—
380
—
380 380 380
—
380
—
1-23
motor
frequency
motor
dependent
105 105 60
—
60
—
105 105 60
—
60
—
105 105 60
—
60
—
1-24
motor
amperage
size
dependent
160 160 35.5
—
35.5
—
184 184 42.6
—
42.6
—
256 256 42.6
—
42.6
—
1-25 motor rpm
size
dependent
6240 6240 1130
—
1130
—
6240 6240 1130
—
1130
—
6240 6240 1130
—
1130
—
1-71
compressor
start delay
0s 00N/A
—
N/A
—
00N/A
—
N/A
—
00N/A
—
N/A
—
1-73 Flying Restart NO N/A N/A 0
—
0
—
N/A N/A 0
—
0
—
N/A N/A 0
—
0
—
1-78
starting
frequency
26hz 26 26 N/A
—
N/A
—
26 26 N/A
—
N/A
—
26 26 N/A
—
N/A
—
1-79
Comp start
maxtime to
trip
5s 55N/A
—
N/A
—
55N/A
—
N/A
—
55N/A
—
N/A
—
1-80
function at
stop
coast 000
—
0
—
000
—
0
—
000
—
0
—
1-90
motor ther-
mal protection
0 000
—
0
—
000
—
0
—
000
—
0
—
3-02 min ref 0 00N/A
—
N/A
—
00N/A
—
N/A
—
00N/A
—
N/A
—
3-03 max reference
size
dependent
75 75 60
—
60
—
85 85 60
—
60
—
95 95 60
—
60
—
3-13 type reference remote 110
—
0
—
110
—
0
—
110
—
0
—
3-15 src ref#1 no function 000
—
0
—
000
—
0
—
000
—
0
—
3-16 src ref#2 no function 000
—
0
—
000
—
0
—
000
—
0
—
3-41 ramp up 100s 100 100 20
—
20
—
100 100 20
—
20
—
100 100 20
—
20
—
3-42 ramp down 100s 100 100 20
—
20
—
100 100 20
—
20
—
100 100 20
—
20
—
3-82
starting ramp
time
3s 33N/A
—
N/A
—
33N/A
—
N/A
—
33N/A
—
N/A
—
4-10
motor speed
direct
clockwise 000
—
0
—
000
—
0
—
000
—
0
—
4-12
motor speed
low limit
26Hz 26 26 5
—
5
—
26 26 5
—
5
—
26 26 5
—
5
—
4-14
motor speed
high limit
95Hz 75 75 60
—
60
—
85 85 60
—
60
—
95 95 60
—
60
—
4-16 torque limit
size
dependent
150 150 150
—
150
—
150 150 150
—
150
—
150 150 150
—
150
—
4-18 current limit
size
dependent
110 110 110
—
110
—
110 110 110
—
110
—
110 110 110
—
110
—
4-19
max output
frequency
size
dependent
76 76 N/A
—
N/A
—
86 86 N/A
—
N/A
—
96 96 N/A
—
N/A
—
5-12 DI #27 Coast Inverse 220
—
0
—
220
—
0
—
220
—
0
—
5-19
DI#37 safe
stop
safe stop
alarm
11N/A
—
N/A
—
11N/A
—
N/A
—
11N/A
—
N/A
—
5-40[36] relay 1
control word
bit 11
36 36 N/A
—
N/A
—
36 36 N/A
—
N/A
—
36 36 N/A
—
N/A
—
5-40[5] relay 2 running 55N/A
—
N/A
—
55N/A
—
N/A
—
55N/A
—
N/A
—
8-01 control site
digital & con-
trol word
000
—
0
—
000
—
0
—
000
—
0
—
8-02
control
source
FC
port=RS485
111
—
1
—
111
—
1
—
111
—
1
—
8-03 time out time 10s 10 10 10
—
10
—
10 10 10
—
10
—
10 10 10
—
10
—
8-04
time out func-
tion
stop and trip 552
—
2
—
552
—
2
—
552
—
2
—
14-00 Pattern [AVM] 60AVM N/A N/A 0
—
0
—
N/A N/A 0
—
0
—
N/A N/A 0
—
0
—
14-01
switching
frequency
3kHz 446
—
6
—
446
—
6
—
446
—
6
—
14-03
over-
modulation
yes 11N/A
—
N/A
—
11N/A
—
N/A
—
11N/A
—
N/A
—
14-10 main failure alarm 66N/A
—
N/A
—
66N/A
—
N/A
—
66N/A
—
N/A
—
14-11
Mains voltage
at Mains fault
345V 352 352 N/A
—
N/A
—
352 352 N/A
—
N/A
—
352 352 N/A
—
N/A
—
14-50 RFI Filter on 11N/A
—
N/A
—
11N/A
—
N/A
—
11N/A
—
N/A
—
14-60
function at
overtemp
derate 11N/A
—
N/A
—
11N/A
—
N/A
—
11N/A
—
N/A
—
14-61
inverter
overload
derate 11N/A
—
N/A
—
11N/A
—
N/A
—
11N/A
—
N/A
—