Table 163 — VFD Parameters, High Tier, for 440 V/50 Hz Units, 30XV200-250
NOTE: Compressor motor voltage is 380V.
PARAMETER
SETTING
DESCRIPTION
30XV200 30XV225 30XV250
COMP FAN COMP FAN COMP FAN
NUMBERDESCRIPTION A B A1A2B1B2 A B A1A2B1B2 A B A1A2B1B2
0-40
hand on
button
disabled 00N/A
N/A
0 0 N/A N/A N/A
0 0 N/A N/A N/A N/A
1-03 torque profile
Compressor
Torque
00N/A
N/A
0 0 N/A N/A N/A
0 0 N/A N/A N/A N/A
1-20 motor kW
size
dependent
97 97 16.1
16.1
160 97 9.2 9.2 13.8
160 160 9.2 9.2 9.2 9.2
1-22 motor volts
motor
dependent
380 380 380
380
380 380 380 380 380
380 380 380 380 380 380
1-23
motor
frequency
motor
dependent
105 105 60
60
98 105 60 60 60
98 98 60 60 60 60
1-24
motor
amperage
size
dependent
231 231 49.7
49.7
314 201 28.4 28.4 42.6
300 300 28.4 28.4 28.4 28.4
1-25 motor rpm
size
dependent
6240 6240 1130
1130
5830 6240 1130 1130 1130
5830 5830 1130 1130 1130 1130
1-71
compressor
start delay
0s 00N/A
N/A
0 0 N/A N/A N/A
0 0 N/A N/A N/A N/A
1-73 Flying Restart NO N/A N/A 0
0
N/AN/A000
N/AN/A0000
1-78
starting
frequency
26hz 26 26 N/A
N/A
26 26 N/A N/A N/A
26 26 N/A N/A N/A N/A
1-79
Comp start
maxtime to
trip
5s 55N/A
N/A
5 5 N/A N/A N/A
5 5 N/A N/A N/A N/A
1-80
function at
stop
coast 000
0
00000
000000
1-90
motor ther-
mal protection
0 000
0
00000
000000
3-02 min ref 0 00N/A
N/A
0 0 N/A N/A N/A
0 0 N/A N/A N/A N/A
3-03 max reference
size
dependent
105 105 60
60
83 93 60 60 60
80 80 60 60 60 60
3-13 type reference remote 110
0
11000
110000
3-15 src ref#1 no function 000
0
00000
000000
3-16 src ref#2 no function 000
0
00000
000000
3-41 ramp up 100s 100 100 20
20
100 100 20 20 20
100 100 20 20 20 20
3-42 ramp down 100s 100 100 20
20
100 100 20 20 20
100 100 20 20 20 20
3-82
starting ramp
time
3s 33N/A
N/A
3 3 N/A N/A N/A
3 3 N/A N/A N/A N/A
4-10
motor speed
direct
clockwise 000
0
00000
000000
4-12
motor speed
low limit
26Hz 26 26 5
5
26 26 5 5 5
26265555
4-14
motor speed
high limit
95Hz 105 105 60
60
83 93 60 60 60
80 80 60 60 60 60
4-16 torque limit
size
dependent
150 150 150
150
150 150 150 150 150
150 150 150 150 150 150
4-18 current limit
size
dependent
110 110 110
110
110 110 110 110 110
110 110 110 110 110 110
4-19
max output
frequency
size
dependent
106 106 N/A
N/A
84 94 N/A N/A N/A
81 81 N/A N/A N/A N/A
5-12 DI #27 Coast Inverse 220
0
22000
220000
5-19
DI#37 safe
stop
safe stop
alarm
11N/A
N/A
1 1 N/A N/A N/A
1 1 N/A N/A N/A N/A
5-40[36] relay 1
control word
bit 11
36 36 N/A
N/A
36 36 N/A N/A N/A
36 36 N/A N/A N/A N/A
5-40[5] relay 2 running 55N/A
N/A
5 5 N/A N/A N/A
5 5 N/A N/A N/A N/A
8-01 control site
digital & con-
trol word
000
0
00000
000000
8-02
control
source
FC
port=RS485
111
1
11111
111111
8-03 time out time 10s 10 10 10
10
10 10 10 10 10
10 10 10 10 10 10
8-04
time out func-
tion
stop and trip 552
2
55222
552222
14-00 Pattern [AVM] 60AVM N/A N/A 0
0
N/AN/A000
N/AN/A0000
14-01
switching
frequency
3kHz 446
6
44666
446666
14-03
over-
modulation
yes 11N/A
N/A
1 1 N/A N/A N/A
1 1 N/A N/A N/A N/A
14-10 main failure alarm 66N/A
N/A
6 6 N/A N/A N/A
6 6 N/A N/A N/A N/A
14-11
Mains voltage
at Mains fault
345V 352 352 N/A
N/A
352 352 N/A N/A N/A
352 352 N/A N/A N/A N/A
14-50 RFI Filter on 11N/A
N/A
1 1 N/A N/A N/A
1 1 N/A N/A N/A N/A
14-60
function at
overtemp
derate 11N/A
N/A
1 1 N/A N/A N/A
1 1 N/A N/A N/A N/A
14-61
inverter
overload
derate 11N/A
N/A
1 1 N/A N/A N/A
1 1 N/A N/A N/A N/A