APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
LEGEND
* Depends on the selected language (English by default).
GENUNIT — GENERAL PARAMETERS
Carrier Controller PATH: Main Menu General Parameters
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Local=0 Net.=1 Remote=2 CTRL_TYP 0 to 2 0 — RO
2 Run Status STATUS
Off
Running
Stopping
Delay
Tripout
Ready
Override
Test
——RO
3 Net.: Cmd Start/Stop CHIL_S_S
Disable(0)/
Enable(1)
Disable(0) — RW
4 Net.: Cmd Occupied CHIL_OCC NO(0)/YES(1) NO(0) — RW
5 Minutes Left for Start min_left — 0 min RO
6 Setpoint Select SP_SEL 0 to 2 0 — RW
7 0=Auto, 1=Spt1, 2=Spt2 — — — — —
8 Setpoint Occupied? SP_OCC NO(0)/YES(1) YES(1) — RW
9 Percent Total Capacity CAP_T 0 to 100 0 % RO
LEGEND
RO — Read Only
RW — Read/Write
Spt — Set Point
TEMP — Temperatures
Carrier Controller PATH: Main Menu Temperatures
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Evap Entering Fluid COOL_EWT — — °F (°C) RO
2 Evap Leaving Fluid COOL_LWT — — °F (°C) RO
3 Evap Delta T COOL_DLT — — °F (°C) RO
4 Outdoor Air Temperature OAT — — °F (°C) RO
5 Saturated Cond Tmp Cir A SCT_A — — °F (°C) RO
6 Saturated Suction Temp A SST_A — — °F (°C) RO
7 Saturated Liquid Temp A SLT_A — — °F (°C) RO
8 Compressor Suction Tmp A SUCT_A — — °F (°C) RO
9 Discharge Gas Temp Cir A DGT_A — — °F (°C) RO
10 Motor Temperature Cir A CP_TMP_A — — °F (°C) RO
11 EXV Eco. Tmp Cir A ECO_T_A — — °F (°C) RO
12 Eco. Saturated Tmp A ECO_SATA — — °F (°C) RO
13 Liquid Temperature A LIQ_T_A — — °F (°C) RO
14 Saturated Cond Tmp Cir B SCT_B — — °F (°C) RO
15 Saturated Suction Temp B SST_B — — °F (°C) RO
16 Saturated Liquid Temp B SLT_B — — °F (°C) RO
17 Compressor Suction Tmp B SUCT_B — — °F (°C) RO
18 Discharge Gas Temp Cir B DGT_B — — °F (°C) RO
19 Motor Temperature Cir B CP_TMP_B — — °F (°C) RO
20 EXV Eco. Tmp Cir B ECO_T_B — — °F (°C) RO
21 Eco. Saturated Tmp B ECO_SATB — — °F (°C) RO
22 Liquid Temperature B LIQ_T_B — — °F (°C) RO
23 Space Temp (Opt.) SPACETMP — — °F (°C) RO
24 Chill Water Temp (Opt.) CHWSTEMP — — °F (°C) RO
RO — Read Only
RW — Read/Write