APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
LEGEND
* Depends on the selected language (English by default).
PRESSURE — Pressures
Carrier Controller PATH: Main Menu Pressures
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Discharge Pressure A DP_A — — PSI (kPa) RO
2 Main Suction Pressure A SP_A — — PSI (kPa) RO
3 Oil Pressure A OP_A — — PSI (kPa) RO
4 Delta Oil Pressure A DOP_A — — PSI (kPa) RO
5 Oil Filter Press. Drop A OFDP_A — — PSI (kPa) RO
6 Economizer Pressure A ECO_P_A — — PSI (kPa) RO
7 Liquid Pressure A LIQ_P_A — — PSI (kPa) RO
8 Discharge Pressure B DP_B — — PSI (kPa) RO
9 Main Suction Pressure B SP_B — — PSI (kPa) RO
10 Oil Pressure B OP_B — — PSI (kPa) RO
11 Delta Oil Pressure B DOP_B — — PSI (kPa) RO
12 Oil Filter Press. Drop B OFDP_B — — PSI (kPa) RO
13 Economizer Pressure B ECO_P_B — — PSI (kPa) RO
14 Liquid Pressure B LIQ_P_B — — PSI (kPa) RO
INPUTS — Inputs Status
Carrier Controller PATH: Main Menu Inputs Status
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Remote On/Off Switch ONOFF_SW Open(0)/Closed(1) Open(0) — RO
2 Remote Setpoint Switch SETP_SW Open(0)/Closed(1) Open(0) — RO
3 Limit Switch 1 LIM_SW1 Open(0)/Closed(1) Open(0) — RO
4 Limit Switch 2 LIM_SW2 Open(0)/Closed(1) Open(0) — RO
5 Oil Level Input A OIL_L_A Open(0)/Closed(1) Open(0) — RO
6 Oil Level Input B OIL_L_B Open(0)/Closed(1) Open(0) — RO
7 Remote Reset Setpoint SP_RESET — — mA RO
8 Remote Dem. Limit LIM_ANAL — — mA RO
9 Leakage Detector 1 leak_v — — Volts RO
10 Leakage Detector 2 leak_2_v — — Volts RO
11 Customer Interlock REM_LOCK Open(0)/Closed(1) Open(0) — RO
12 Ice Done Storage Switch ICE_SW Open(0)/Closed(1) Open(0) — RO
13 Occupied Override Switch OCC_OVSW Open(0)/Closed(1) Open(0) — RO
14 Evap Heater Detector HEATR_SW Open(0)/Closed(1) Open(0) — RO
RO — Read Only
RW — Read/Write