260
APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
LEGEND
* Depends on the selected language (English by default).
SCRN_BRT — Screen Brightness Table
Carrier Controller PATH:
Main Menu  Configuration Menu
HMI Configuration  Screen Brightness Table
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Adjust Display Brightness
Very Low(0)
Low(1)
Medium(2)
High(3)
Very High(4)
—RW
USRPWCHG — User Password Change Table
Carrier Controller PATH:
Main Menu  Configuration Menu
HMI Configuration  User Password Change Table
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Your login password —RW
2 New user password —RW
3 Confirm new user password —RW
GEN_CONF — General Configuration Table
Carrier Controller PATH:
Main Menu  Configuration Menu
General Configuration Table
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1 Cir Priority Sequence prio_cir
Auto(0)
0—RWA Priority(1)
B Priority(2)
2 Ramp Loading Enabled ramp_sel No(0)/Yes(1) Yes(1) RW
3 Unit Off to On Delay off_on_d 1 to 15 1 min RW
4 Demand Limit Type Select lim_sel
None(0)
0—
RW
Switch(1) RW
4-20mA(2) RW
5 Night Mode Start Hour nh_start 0 to 23 0 RW
6 Night Mode End Hour nh_end 0 to 23 0 RW
7 Night Capacity Limit nh_limit 0 to 100 100 % RW
8 Ice Mode Enable ice_cnfg No(0)/Yes(1) No(0) RW
9 Short Cycle Management shortcyc No(0)/Yes(1) No(0) RW