APPENDIX A — CARRIER CONTROLLER DISPLAY TABLES (cont)
LEGEND
* Depends on the selected language (English by default).
PUMPCONF — Pump Configuration Table
Carrier Controller PATH:
Main Menu Configuration Menu
Pump Configuration
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Evap Pumps Sequence cpumpseq
No Pump(0)
Two Pumps
Auto(2)
—RW
One Pump Only(1)
Two Pumps Auto(2)
Pump#1 Manual(3)
Pump#2 Manual(4)
2
Pump Auto Rotation Delay pump_del 24-3000
48 Hours
RW
3
Pump Sticking Protection pump_per No(0)/Yes(1)
No(0) —
RW
4
Flow Check if Pump Off pump_loc No(0)/Yes(1)
Yes(1) —
RW
RESETCFG — Reset Configuration Table
Carrier Controller PATH:
Main Menu Configuration Menu
Reset Configuration Table
LINE DISPLAYED TEXT* CCN NAME RANGE
DEFAULT
VALUE
UNIT
READ/
WRITE
1
Cooling Reset Select cr_sel
None(0)
None(0) — RW
OAT(1)
Delta T(2)
4-20mA(3)
Space Temp(4)
2
OAT No Reset Value oat_crno 14 to 125(-10 to 51.7)
14(-10) °F(°C) RW
3
OAT Full Reset Value oat_crfu 14 to 125(-10 to 51.7)
14(-10) °F(°C) RW
4
Delta T No Reset Value dt_cr_no 0 to 25(-17.8 to -3.9)
0(-17.8) °F(°C) RW
5
Delta T Full Reset Value dt_cr_fu 0 to 25(-17.8 to -3.9)
0(-17.8) °F(°C) RW
6
Current No Reset Value v_cr_no 0 to 20
0mARW
7
Current Full Reset Value v_cr_fu 0 to 20
0mARW
8
Space T No Reset Value spacr_no 14 to 125(-10 to 51.7)
14(-10) °F(°C) RW
9
Space T Full Reset Value spacr_fu 14 to 125(-10 to 51.7)
14(-10) °F(°C) RW
10
Cooling Reset Deg. Value cr_deg -30 to 30(-34.4 to -1.1)
0(-17.8) °F(°C)
RW — Read/Write